Positioning of the outdoor sensor
H
2/3 x H
Recommended location
Unsuitable location
▪
Position the outdoor sensor on the north or north west side of the
house.
▪
Make sure that the outdoor sensor is not placed in direct sun light.
▪
For taller buildings, the sensor should be positioned between the
second and third floors.
▪
The sensor location must not be completely protected from the
wind but not placed in a direct draft.
▪
The outdoor sensor must not be placed on reflective panel walls.
▪
The sensor must be positioned at least 1 m from openings in the
walls which may emit hot air.
▪
If the sensor cable is connected through a pipe, the pipe must be
sealed so that the sensor is not affected by outgoing air.
Commissioning
DHP-M
VIJSE302
Danfoss Heating Solutions
12