6.1.3
Testing the system pump
1. Enable the system pump by pressing
(manual enable).
2. Start the system pump by pressing
(on/off).
3. Check that the system pump is running by:
▪
listening
▪
placing a hand on the pump
▪
listening for air
4. Bleed the system if necessary. See chapter 'Filling and bleeding the water heater and heating system'
5. Stop the system pump by pressing
.
6.1.4
Testing the compressor
1. Enable the compressor by pressing
(manual enable).
2. Set compressor gear.
3. Check that there is no abnormal noise.
4. Check that the pressure pipe becomes hot.
5. Stop the compressor by pressing
(manual enable).
6.1.5
Exiting manual test
To exit manual test:
1. Press
on the Start screen to open the Menu screen.
2. Press on Settings
.
3. Press to go to the menu page for Manual test.
4. Press on the text Manual test.
5. Press
to exit manual test.
The
symbol disappears.
6.1.6
Insulating pipes
When the manual test is completed, a check for leaks should be carried out. When the leakage check has been successfully completed,
the pipes should be insulated.
Caution
Ensure that the pipes which transport cold water are properly insula-
ted to prevent condensation damage.
Commissioning
DHP-M
Danfoss Heating Solutions
VIJSE302
25
Содержание DHP-M
Страница 1: ...MAKING MODERN LIVING POSSIBLE Commissioning DHP M www heating danfoss com...
Страница 36: ...Commissioning DHP M VIJSE302 Danfoss Heating Solutions 36...
Страница 37: ...Commissioning DHP M Danfoss Heating Solutions VIJSE302 37...
Страница 38: ...Commissioning DHP M VIJSE302 Danfoss Heating Solutions 38...
Страница 39: ...Commissioning DHP M Danfoss Heating Solutions VIJSE302 39...