background image

16

Installation, operation and maintenance instructions - VMGFE102

• 

Install thermometers in both the entering and leaving 
water connections.

• 

Install drain connections at all low points to allow the 
whole circuit to be drained.

• 

Install stop valves, close to the entering and leaving 
water connections.

• Use 

fl exible connections to reduce vibration transmis-

sion.

• 

Insulate all pipework, after testing for leaks, both to 
reduce thermal leaks and to prevent condensation.

• 

Wrap the insulations with a demisting screen.

• 

If the external unit water pipes are in an area where the 
ambient temperature is likely to fall below 0°C, they 
must be protected against frost (frost protection 
solution or electric heaters).

NOTE: For units not equipped with a hydronic module a 
screen fi lter must be installed. This must be installed on the 
water entering pipes upstream of the pressure gauge. It must be 
located in a position that is easily accessible for removal and 
cleaning. The mesh size of the fi lter must be 1.2 mm.

The plate heat exchanger can foul up quickly at the initial unit 
start-up, as it complements the fi lter function, and the unit 
operation will be impaired (reduced water fl ow rate due to 
increased pressure drop).

Units with hydronic module are equipped with this type of 
fi lter.

Do not introduce any signifi cant static or dynamic pressure 
into the heat exchange circuit (with regard to the design 
operating pressures).

The products that may be added for thermal insulation of the 
containers during the water piping connection procedure 
must be chemically neutral in relation to the materials and 
coatings to which they are applied.

11.2 - Hydronic connections

The hydronic circuit diagram shows a typical hydronic 
installation. When charging the water circuit use air vents to 
evacuate any residual air pockets.

11.3 - Frost protection

The plate heat exchangers, the piping and the hydronic 
module pump can be damaged by frost, despite the built-in 
anti-freeze protection of the units.

Frost protection of the plate heat exchanger and all hydronic 
circuit components is guaranteed:
• 

Down to -20°C by electric heaters (heat exchanger and 
internal piping) that have an automatic supply (units 
without hydronic module),

• 

Down to -10°C by an electric heater on the heat 
exchanger that has an automatic supply and by pump 
cycling (units with hydronic module),

• 

Down to -20°C by electric heaters (heat exchanger and 
internal piping) that have an automatic supply and by 
pump cycling (units with hydronic module and 
“Reinforced frost protection” option).

Never switch off  the water heat exchanger and hydronic 
circuit heaters or the pump, otherwise frost protection 
can-not be guaranteed. For this reason the main unit 
disconnect switch as well as the auxiliary protection switch 
for the heaters must always be left closed (for the location of 
these components see the wiring diagram).

To ensure frost protection of the units with hydronic module 
water circulation in the water circuit must be maintained by 
periodically switching on the pump. If a shut-off  valve is 
installed, a bypass must be included as shown below.

Winter position

Water 

network

Unit

Closed

Closed

Open

IMPORTANT: Depending on the atmospheric conditions in 
your area you must do the following when switching the unit 
off  in winter:

• 

Add ethylene glycol or propylene glycol with an adequate 
concentration to protect the installation up to a 
temperature of 10 K below the lowest temperature likely to 
occur at the installation site.

• 

If the unit is not used for an extended period, it should be 
drained, and ethylene glycol or propylene glycol should be 
charged in the heat exchanger as a safety precaution, using 
the water inlet purge valve connection.

• 

At the start of the next season, refi ll the unit with water and 
add an inhibitor.

• 

For the installation of auxiliary equipment, the instal-ler 
must comply with basic regulations, especially for 
minimum and maximum fl ow rates, which must be 
between the values listed in the operating limit table 
(application data).

• 

To prevent corrosion by diff erential aeration, the complete 
drained heat transfer circuit must be charged with nitrogen 
for a period of one month.

11.4 - Protection against cavitation (option 116)

To ensure the durability of the pumps in the integrated 
hydronic modules, the control algorithm of the AR05 units 
incorporates anti-cavitation protection.

It is therefore necessary to ensure a minimum pump entering 
pressure of 60 kPa (0.6 bar) during operation and at shut-
down. A pressure below 60 kPa will prohibit unit start-up or 
cause an alarm with the unit shutting down. In order to 
obtain suffi

  cient pressure, it is recommended:

• 

to pressurise the hydronic circuit between 100 kPa and 
400 kPa (1 and 4 bar) maximum on the suction side of 
the pump,

• 

to clean the hydronic circuit before charging water (see 
chapters 12.5 and 12.6),

• 

to regularly clean the screen fi lter,

ATTENTION: The use the integrated hydronic kits for an open 
loop is prohibited.

Содержание AR05 017 Series

Страница 1: ...t Pumps Nominal cooling capacity 40 150 kW Nominal heating capacity 40 160 kW 50 Hz For the operation of the control please refer to the Control manual for the AR05 017 160 series Installation operati...

Страница 2: ...wer supply 14 10 3 Voltage phase imbalance 14 10 4 Recommended wire sections 14 10 5 Field control wiring 15 10 6 Power supply 15 11 WATER CONNECTIONS 15 11 1 Operating precautions and recommendations...

Страница 3: ...Refrigerant 26 14 10 High pressure safety switch 26 14 11 Receiver 26 14 12 Four way valve 26 15 OPTIONS AND ACCESSORIES 27 14 13 Control box 27 16 STANDARD MAINTENANCE 28 16 1 Level 1 maintenance 28...

Страница 4: ...e declarations of conformity for these products 1 2 Check equipment received Inspect the unit for damage or missing parts If damage is detected or if shipment is incomplete immediately le a claim with...

Страница 5: ...hat ensures that people and property are not exposed to refrigerant leaks These uids may be di used in the air but far away from any building air intake or they must be discharged in a quantity that i...

Страница 6: ...that has leaked is generally lower than its original calibration The new calibration may a ect the operating range To avoid nuisance trippingorleaks replaceorre calibratethevalve OPERATING CHECKS IMPO...

Страница 7: ...is running Be sure pressure is at 0 kPa before removing components or opening a circuit Do not attempt to repair or recondition any safety devices when corrosion or build up of foreign material rust d...

Страница 8: ...refer to the chapter Dimensions and clearances to con rm that there is adequate space for all connections and serviceoperations Forthecentreofgravitycoordinates the position of the unit mounting holes...

Страница 9: ...the location of xing points weight distribution and coordinates of the centre of gravity refer to the certi ed dimensional drawings B In multiple unit installations maximum four units the side clearan...

Страница 10: ...of the centre of gravity refer to the certi ed dimensional drawings B In multiple unit installations maximum four units the side clearance between the units should be increased from 1000 to 2000 mm C...

Страница 11: ...hown is a guideline only To nd out the unit refrigerant charge please refer to the unit nameplate In accordance with ISO 9614 1 for information only The values have been rounded and are for informatio...

Страница 12: ...onsidered always contact your local Danfoss representative The required protection level for this class is IP43BW according to reference document IEC 60529 All AR05 units are protected to IP44CW and f...

Страница 13: ...o add a storage tank to the circuit This tank should be equipped with ba es to allow mixing of the uid water or brine Please refer to the examples below 9 2 Operating range standard units heating mode...

Страница 14: ...Pure water litres 600 400 200 1680 1120 560 10 ethylene glycol l 450 300 150 1260 840 420 20 ethylene glycol l 330 220 110 930 620 310 30 ethylene glycol l 270 180 90 750 500 250 40 ethylene glycol l...

Страница 15: ...replaced more frequently every 15000 operating hours instead of 25000 hours for an appliacation using water Recommendations on heat exchange uids No NH4 ammonium ions in the water they are very detrim...

Страница 16: ...hanger and internal piping that have an automatic supply and by pump cycling units with hydronic module and Reinforced frost protection option Never switch o the water heat exchanger and hydronic circ...

Страница 17: ...t leaving pressure information see installation manual Check valve Note x 2 for a dual pump not provided for a single pump Plate heat exchanger Water heat exchanger frost protection heater Installatio...

Страница 18: ...et and outlet item 19 As the total system pressure drop is not known exactly at the start up the water ow rate must be adjusted with the control valve to obtain the speci c ow rate for this system Hyd...

Страница 19: ...e connected to the unit inlet and outlet item 19 Let the pump run for two consecutive hours to clean the hydronic circuit of the system presence of solid contaminants Take another reading Compare this...

Страница 20: ...er is not contaminated Pressure di erential set point control procedure Once the circuit has been cleaned select the hydronic circuit con guration for which the unit selection has been made in general...

Страница 21: ...rate that the maximum value or a higher frequency than the maximum value the system settles at the maximum ow rate or maximum frequency and this results in a higher delta T value than the set point H...

Страница 22: ...05 120 160 Pressure drop kPa Pressure drop kPa Water ow rate l s Water ow rate l s Water ow rate l s Water ow rate l s Legend 1 AR05 039 2 AR05 045 3 AR05 050 4 AR05 060 5 AR05 070 6 AR05 078 Legend 1...

Страница 23: ...AR05 039 2 AR05 045 3 AR05 050 4 AR05 060 5 AR05 070 6 AR05 078 Legend 1 AR05 080 2 AR05 090 3 AR05 100 4 AR05 120 5 AR05 140 Legend 1 AR05 039 2 AR05 045 3 AR05 050 4 AR05 060 5 AR05 070 6 AR05 078...

Страница 24: ...peration of two units in master slave mode The control of a master slave assembly is in the entering water and does not require any additional sensors standard con guration It can also be located in t...

Страница 25: ...capacity of the heat pump at 7 C outdoor air temperature This requires only a 400 V 3 ph 50 Hz power supply source as well as a connection to the unit via a communication bus For the required con gura...

Страница 26: ...densables in the system The presence of moisture changes the colour of the indicator paper in the sight glass 14 7 Filter drier This is a one piece brazed lter drier located in the liquid line The rol...

Страница 27: ...complies with JBus protocol Easy connection by communication bus to a building management system AR05 039 160 Bacnet gateway 148C Two directional communications board complies with Bacnet protocol Eas...

Страница 28: ...hly or annually depending on the veri cation type In these conditions the following maintenance operations are recommended Carry out all level 1 operations then Electrical checks At least once a year...

Страница 29: ...Contactor LC1D12B7 KM 1 7 Contactor LC1D18B7 1 7 Contactor LC1D25B7 2 5 Tunnel terminal screw compressor circuit breaker Circuit breaker 25507 QM 3 6 Circuit breaker 25508 Circuit breaker 25509 Tunne...

Страница 30: ...perations 16 7 Water heat exchanger maintenance Check that the insulating foam is intact and securely in place the cooler heaters are operating secure and correctly positioned the water side connectio...

Страница 31: ...nt check Is there any shipping damage If so where Will this damage prevent unit start up Unit is level in its installation Power supply agrees with the unit name plate Electrical circuit wiring has be...

Страница 32: ...nal kW capacity for process cooling Proper loop volume established Proper loop corrosion inhibitor included litres of Proper loop freeze protection included if required litres of Water piping includes...

Страница 33: ...t in the LOCAL ON position Unit starts and operates properly Temperatures and pressures WARNING Once the machine has been operating for a while and the temperatures and pressures have stabilized recor...

Страница 34: ...34 Installation operation and maintenance instructions VMGFE102 VMGFE102...

Отзывы: