background image

15

Installation, operation and maintenance instructions - VMGFE102

IMPORTANT: Before connection of  the main power cables (L1 
- L2 - L3) on the terminal block, it is impera-tive to check the 
correct order of the 3 phases before pro-ceeding to the 
connection on the main disconnect/isolator switch.

Power cable entry

The power cables can enter the control box from below or 
from the side of the unit, at the bottom of the angle iron. 
Pre-punched holes facilitate the entry. Refer to the certifi ed 
dimensional drawing for the unit. A removable aluminium 
plate below the control box allows introduction of the cables.

10.5 - Field control wiring

Refer to the AR05 017-160 Controls IOM and the certifi ed 
wiring diagram supplied with the unit for the fi eld control 
wiring of the following features:
• 

Water heat exchanger pump interlock (mandatory)

• Remote 

on/off  switch

• 

Demand limit external switch

• 

Remote dual set point

• 

Alarm, alert and operation report

• Heating/cooling 

selection

10.6 - Power supply

ATTENTION: After the unit has been commissioned, the power 
supply must only be disconnected for quick main-tenance 
operations (one day maximum). For longer main-tenance 
operations or when the unit is taken out of service and stored 
(e.g. during the winter or if the unit does not need to generate 
cooling) the power supply must be main-tained to ensure 
supply to the heaters (compressor oil crankcase heaters, unit 
frost protection).

After all possible options have been connected, the trans-
former ensures the availability of a usable 24 VA or 1 A power 
reserve for the control circuit on site.

11  WATER CONNECTIONS

For size and position of the unit water inlet and outlet 
con-nections refer to the certifi ed dimensional drawings 
supplied with the unit. The water pipes must not transmit any 
radial or axial force to the heat exchangers nor any vibration. 

The water supply must be analysed and appropriate fi lter-
ing, treatment, control devices, shut-off  and bleed valves and 
circuits built in, to prevent corrosion (example: damage to the 
protection of the tube surface if the fl uid is polluted), fouling 
and deterioration of the pump fi ttings.

Before any start-up verify that the heat exchange fl uid is 
compatible with the materials and the water circuit coating.

In case additives or other fl uids than those recommended by 
Danfoss are used, ensure that the fl uids are not considered as 
a gas, and that they belong to class 2, as defi ned in direc-tive 
97/23/EC.

The pumps in the hydronic module are compatible with 40% 
propylene glycol and 40% ethylene glycol. But if these fl uids 
are used, the pump fi ttings need to be replaced more 
frequently (every 15000 operating hours instead of 25000 
hours for an appliacation using water).

Recommendations on heat exchange fl uids:

• No 

NH

4+

 ammonium ions in the water, they are very 

detrimental for copper. This is one of the most impor-
tant factors for the operating life of copper piping. A 
content of several tenths of mg/l will badly corrode the 
copper over time.

• Cl

-

 Chloride ions are detrimental for copper with a risk of 

perforations by corrosion by puncture. If possible keep 
below 10 mg/l.

• SO

4

2-

 sulphate ions can cause perforating corrosion, if 

their content is above 30 mg/l.

• No 

fl uoride ions (<0.1 mg/l).

• No 

Fe

2+

 and Fe

3+

 ions with non negligible levels of dis-

solved oxygen must be present. Dissolved iron < 5 mg/l 
with dissolved oxygen < 5 mg/l.

• 

Dissolved silicon: silicon is an acid element of water and 
can also lead to corrosion risks. Content < 1mg/l.

• 

Water hardness:  >0.5 mmol/l. Values between 1 and 2.5 
mmol/l can be recommended. This will facilitate scale 
deposit that can limit corrosion of copper. Values that are 
too high can cause piping blockage over time. A total 
alkalimetric titre (TAC) below 100 is desirable.

• 

Dissolved oxygen: Any sudden change in water oxyge-
nation conditions must be avoided. It is as detrimental 
to deoxygenate the water by mixing it with inert gas as it 
is to over-oxygenate it by mixing it with pure oxygen. The 
disturbance of the oxygenation conditions encou-rages 
destabilisation of copper hydroxides and enlarge-ment of 
particles.

• Specifi c resistance - electric conductivity: the higher the 

specifi c resistance, the slower the corrosion tendency. 
Values above 30 Ohm·m are desirable. A neutral 
environment favours maximum specifi c resistance 
values. For electric conductivity values in the order of 
20-60 mS/m can be recommended.

• 

pH: Ideal case pH neutral at 20-25°C (7 < pH < 8).

ATTENTION: Charging, adding or draining fl uid from the water 
circuit must be done by qualifi ed personnel, using air vents and 
materials suitable for the products. Water circuit charging 
devices are fi eld-supplied. Charging and removing heat 
exchange fl uids should be done with devices that must be 
included on the water circuit by the installer. Never use the 
unit heat exchangers to add heat exchange fl uid.

11.1 - Operating precautions and recommendations

The water circuit should be designed to have the least number of 
elbows and horizontal pipe runs at diff erent levels. Below the 
main points to be checked for the connection:
• 

Comply with the water inlet and outlet connections 
shown on the unit.

• 

Install manual or automatic air purge valves at all high 
points in the circuit.

• 

Use an expansion device to maintain pressure in the 
system and install a safety valve and an expansion tank.

• 

Units with a hydronic module include the safety valve 
and the expansion tank.

Содержание AR05 017 Series

Страница 1: ...t Pumps Nominal cooling capacity 40 150 kW Nominal heating capacity 40 160 kW 50 Hz For the operation of the control please refer to the Control manual for the AR05 017 160 series Installation operati...

Страница 2: ...wer supply 14 10 3 Voltage phase imbalance 14 10 4 Recommended wire sections 14 10 5 Field control wiring 15 10 6 Power supply 15 11 WATER CONNECTIONS 15 11 1 Operating precautions and recommendations...

Страница 3: ...Refrigerant 26 14 10 High pressure safety switch 26 14 11 Receiver 26 14 12 Four way valve 26 15 OPTIONS AND ACCESSORIES 27 14 13 Control box 27 16 STANDARD MAINTENANCE 28 16 1 Level 1 maintenance 28...

Страница 4: ...e declarations of conformity for these products 1 2 Check equipment received Inspect the unit for damage or missing parts If damage is detected or if shipment is incomplete immediately le a claim with...

Страница 5: ...hat ensures that people and property are not exposed to refrigerant leaks These uids may be di used in the air but far away from any building air intake or they must be discharged in a quantity that i...

Страница 6: ...that has leaked is generally lower than its original calibration The new calibration may a ect the operating range To avoid nuisance trippingorleaks replaceorre calibratethevalve OPERATING CHECKS IMPO...

Страница 7: ...is running Be sure pressure is at 0 kPa before removing components or opening a circuit Do not attempt to repair or recondition any safety devices when corrosion or build up of foreign material rust d...

Страница 8: ...refer to the chapter Dimensions and clearances to con rm that there is adequate space for all connections and serviceoperations Forthecentreofgravitycoordinates the position of the unit mounting holes...

Страница 9: ...the location of xing points weight distribution and coordinates of the centre of gravity refer to the certi ed dimensional drawings B In multiple unit installations maximum four units the side clearan...

Страница 10: ...of the centre of gravity refer to the certi ed dimensional drawings B In multiple unit installations maximum four units the side clearance between the units should be increased from 1000 to 2000 mm C...

Страница 11: ...hown is a guideline only To nd out the unit refrigerant charge please refer to the unit nameplate In accordance with ISO 9614 1 for information only The values have been rounded and are for informatio...

Страница 12: ...onsidered always contact your local Danfoss representative The required protection level for this class is IP43BW according to reference document IEC 60529 All AR05 units are protected to IP44CW and f...

Страница 13: ...o add a storage tank to the circuit This tank should be equipped with ba es to allow mixing of the uid water or brine Please refer to the examples below 9 2 Operating range standard units heating mode...

Страница 14: ...Pure water litres 600 400 200 1680 1120 560 10 ethylene glycol l 450 300 150 1260 840 420 20 ethylene glycol l 330 220 110 930 620 310 30 ethylene glycol l 270 180 90 750 500 250 40 ethylene glycol l...

Страница 15: ...replaced more frequently every 15000 operating hours instead of 25000 hours for an appliacation using water Recommendations on heat exchange uids No NH4 ammonium ions in the water they are very detrim...

Страница 16: ...hanger and internal piping that have an automatic supply and by pump cycling units with hydronic module and Reinforced frost protection option Never switch o the water heat exchanger and hydronic circ...

Страница 17: ...t leaving pressure information see installation manual Check valve Note x 2 for a dual pump not provided for a single pump Plate heat exchanger Water heat exchanger frost protection heater Installatio...

Страница 18: ...et and outlet item 19 As the total system pressure drop is not known exactly at the start up the water ow rate must be adjusted with the control valve to obtain the speci c ow rate for this system Hyd...

Страница 19: ...e connected to the unit inlet and outlet item 19 Let the pump run for two consecutive hours to clean the hydronic circuit of the system presence of solid contaminants Take another reading Compare this...

Страница 20: ...er is not contaminated Pressure di erential set point control procedure Once the circuit has been cleaned select the hydronic circuit con guration for which the unit selection has been made in general...

Страница 21: ...rate that the maximum value or a higher frequency than the maximum value the system settles at the maximum ow rate or maximum frequency and this results in a higher delta T value than the set point H...

Страница 22: ...05 120 160 Pressure drop kPa Pressure drop kPa Water ow rate l s Water ow rate l s Water ow rate l s Water ow rate l s Legend 1 AR05 039 2 AR05 045 3 AR05 050 4 AR05 060 5 AR05 070 6 AR05 078 Legend 1...

Страница 23: ...AR05 039 2 AR05 045 3 AR05 050 4 AR05 060 5 AR05 070 6 AR05 078 Legend 1 AR05 080 2 AR05 090 3 AR05 100 4 AR05 120 5 AR05 140 Legend 1 AR05 039 2 AR05 045 3 AR05 050 4 AR05 060 5 AR05 070 6 AR05 078...

Страница 24: ...peration of two units in master slave mode The control of a master slave assembly is in the entering water and does not require any additional sensors standard con guration It can also be located in t...

Страница 25: ...capacity of the heat pump at 7 C outdoor air temperature This requires only a 400 V 3 ph 50 Hz power supply source as well as a connection to the unit via a communication bus For the required con gura...

Страница 26: ...densables in the system The presence of moisture changes the colour of the indicator paper in the sight glass 14 7 Filter drier This is a one piece brazed lter drier located in the liquid line The rol...

Страница 27: ...complies with JBus protocol Easy connection by communication bus to a building management system AR05 039 160 Bacnet gateway 148C Two directional communications board complies with Bacnet protocol Eas...

Страница 28: ...hly or annually depending on the veri cation type In these conditions the following maintenance operations are recommended Carry out all level 1 operations then Electrical checks At least once a year...

Страница 29: ...Contactor LC1D12B7 KM 1 7 Contactor LC1D18B7 1 7 Contactor LC1D25B7 2 5 Tunnel terminal screw compressor circuit breaker Circuit breaker 25507 QM 3 6 Circuit breaker 25508 Circuit breaker 25509 Tunne...

Страница 30: ...perations 16 7 Water heat exchanger maintenance Check that the insulating foam is intact and securely in place the cooler heaters are operating secure and correctly positioned the water side connectio...

Страница 31: ...nt check Is there any shipping damage If so where Will this damage prevent unit start up Unit is level in its installation Power supply agrees with the unit name plate Electrical circuit wiring has be...

Страница 32: ...nal kW capacity for process cooling Proper loop volume established Proper loop corrosion inhibitor included litres of Proper loop freeze protection included if required litres of Water piping includes...

Страница 33: ...t in the LOCAL ON position Unit starts and operates properly Temperatures and pressures WARNING Once the machine has been operating for a while and the temperatures and pressures have stabilized recor...

Страница 34: ...34 Installation operation and maintenance instructions VMGFE102 VMGFE102...

Отзывы: