AK-CC 750A
RS8HP102 © Danfoss 2018-09
97
AD – Flash gas evapora.
A,B,C,D
Low
AD – Flash gas detect A,B,C,D
Flash gas has been detected at the valve for a relatively long time
General alarms
Thermostat x – Low temp.
alarm
Low
Thermostat x - Low alarm
The temperature for thermostat no. x has been below the low alarm limit for longer time than set delay
Thermostat x – High temp.
alarm
Low
Thermostat x - High alarm
The temperature for thermostat no. x has been above the high alarm limit for longer time than set delay
Pressostat x – Low pressure
alarm
Low
Pressostat x - Low alarm
The pressure for pressostat no. x has been below the low alarm limit for longer time than set delay
Pressostat x – High pressure
alarm
Low
Pressostat x - High alarm
The pressure for pressostat no. x has been above the high alarm limit for longer time than set delay
Voltage input x – Low alarm
Low
Analog input x - Low alarm
The voltage signal has been below the low alarm limit for longer time than set delay
Voltage input x – High alarm
Low
Analog input x - High alarm
The voltage signal has been above the high alarm limit for longer time than set delay
DIx alarm input
Low
DIx alarm
Alarm on general alarm input DI x
Stepper valve
High
Stepper - Inj. A, B, C. D.
Open coil, Shorted output,
Error, Power failure
Check supply to the actual valve
System alarms
The alarm priority can not be altered on system alarms
Medium
Clock has not been set
Time has not been set
Medium
System Critical exception
A unrecoverable critical system failure has occurred – exchange the controller
Medium
System alarm exception
A minor system failure has occurred – power off controller
Medium
Alarm destination disabled
When this alarm is activated the alarm transmission to the alarm receiver has been deactivated.
When the alarm is cleared the alarm transmission to the alarm receiver has been activated.
Medium
Alarm route failure
Alarms can not be transmitted to alarm receiver – check communication
High
Alarm router full
The internal alarm buffer has an overrun – this might occur if the controller can not send the alarms to the alarm
receiver. Check communication between controller and AKA gateway.
Medium
Device is restarting
The controller is restarting after flash updating of the software
Medium
IO module error
There is a communication fault between the controller module and the extension modules – the fault must be cor-
rected as soon as possible
Low
Manual override IO
The input/ output in question has been put in manual control mode via the AK-ST 500 service tool software