AK-CC 750A
RS8HP102 © Danfoss 2018-09
19
Signal
Module
Point
Terminal
Signal type /Active at
1
(AI 1)
1 - 2
2
(AI 2)
3 - 4
3
(AI 3)
5 - 6
4
(AI 4)
7 - 8
5
(AO 1)
17 - 18
6
(AO 2)
19 - 20
7
(AO 3)
21 - 22
8
(AO 4)
23 - 24
Signal
Signal
type
S
Pt 1000 ohm/0°C
S2
S3
S4
S4
S5
Saux
Pt 1000
P
AKS 32R
AKS 32
P0
Paux
AKS 32R /
AKS 2050
MBS 8250
-1 - xx bar
AKS 32
-1 - zz bar
U
...
0 - 5 V
0 - 10 V
On/Off
Ext.
Main
switch
Day/
Night
Door
Level
switch
Active at:
Closed
/
Open
AO
0-10 V
Point
5
6
7
8
Type
AO1
AO2
AO3
AO4
Point
1
2
3
4
Type
AI1
AI2
AI3
AI4
Point
Terminal 9:
12 V
Terminal 10:
5 V
Terminal
11, 12:
(Cable screen)
The screen on the pressure
transmitter cables must only
be connected at the end of the
controller.
Galvanic isolation:
AI 1-4 ≠ AO 1-2 ≠ AO 3-4
At the top the
signal input is
the left of the
two terminals.
At the bottom
the signal input
is the right of the
two terminals.
3: Brown
2: Blue
1: Black
3: Brown
2: Black
1: Red