AK-CC 750 - 080Z0130 & 080Z0139
RS8GM222 © Danfoss 10-2014
35
Supply voltage
Supply voltage is only connected to the controller module. The
supply to the other modules is transmitted via the plug between
the modules. The supply must be 24 V +/-20%. One transformer
must be used for each controller. The transformer must be a class
II. The 24 V must not be shared by other controllers or units. The
analog inputs and outputs are not galvanically separated from the
supply.
The + and – 24V input must not be earthed.
Transformer size
The power consumption grows with the number of modules used:
Module
Type
Number á
Effect
Controller
1 x 8 =
8 VA
Extension module
200-series
_ x 5 =
__ VA
Extension module
100-series
_ x 2 =
__ VA
Total
___
VA
12
Example continued:
Controller module
8 VA
+ 1 extension module in 100-series
2 VA
------
Transformer size (least)
10 VA