54
RS8GM222 © Danfoss 10-2014
AK-CC 750 - 080Z0130 & 080Z0139
5. Configuration of Analog
Input signals
Configuration - continued
We set up the analog inputs for the sensors.
5 - Analog inputs
The possible signals are the
following:
Temperature sensors
:
S2 Evaporating temp.
(A,B,C,D)
S3 Air temp. before evapo-
rator
(A,B,C,D)
S4 Air temp. after evapora-
tor (A,B,C,D)
S5-1 Defrost sensor
(A,B,C,D)
S5-2 Defrost sensor
(A,B,C,D)
Product temperature
(A,B,C,D)
Setting:
• Pt1000
• PTC 1000
Pressure transmitters:
P0 evaporator pressure
Pc Cond. pressure
Paux 1 - 3
Setting:
• AKS 32, -1 – 6 Bar
• AKS 32R, -1 – 6 Bar
• AKS 32, - 1 – 9 Bar
• AKS 32R, -1 – 9 Bar3
• AKS 32, - 1 – 12 Bar
• AKS 32R, -1 – 12 Bar
• AKS 32, - 1 – 20 Bar
• AKS 32R, -1 – 20 Bar
• AKS 32, - 1 – 34 Bar
• AKS 32R, -1 – 34 Bar
• AKS 32, - 1 – 50 Bar
• AKS 32R, -1 – 50 Bar
• AKS 2050, 1 – 59 Bar
• AKS 2050, -1 – 99 bar
• AKS 2050, -1 – 159 bar
Voltage signals for reference
displacement:
Ext. Ref. Signal
Setting:
• 0 - 5 V,
• 1 - 5 V,
• 0 -10 V,
• 2 - 10 V
Sensor
Input
Module Point
Type
Air temperature
S3 A
AI1
1
1
Pt 1000
Air temperature
S3 B
AI2
1
2
Pt 1000
Air temperature
S3 C
AI3
1
3
Pt 1000
Air temperature
S4 A
AI4
1
4
Pt 1000
Air temperature
S4 B
AI5
1
5
Pt 1000
Air temperature
S4 C
AI6
1
6
Pt 1000
Defrost sensor
S5 A
AI7
1
7
Pt 1000
Defrost sensor
S5 B
AI8
1
8
Pt 1000
Defrost sensor
S5 C
AI9
1
9
Pt 1000
Gas temperature
-S2 A
AI10
1
10
Pt 1000
Evaporating pressure
- P0
AI11
1
11
AKS32R-12
Gas temperature
-S2 B
AI1
2
1
Pt 1000
Gas temperature
-S2 C
AI2
2
2
Pt 1000