52
RS8GM222 © Danfoss 10-2014
AK-CC 750 - 080Z0130 & 080Z0139
Configuration - continued
Example:
The settings are shown here in the
display.
5. Set the functions in the third
display
5-
Common functions for door, light etc.
Door switch mode
Select the function of any door switch. The door
switch can be used in one of the following two
ways:
• Alarm only, if the door has been left open for
too long
• Stop refrigeration and fans when the door is
open, along with an alarm if the door has been
left open for too long
Light off delay
Set how long the light should remain on after
the door has been closed (requires a light
control to be set up and controlled via the door
switch)
Restart refrig. delay
Set how long the door may be open before
refrigeration and fans are restarted. Prevents
exposure of the products to too high a tempera-
ture if someone forgets to close the door.
Door alarm delay
If the door has been open for more than the time
delay set here, a door alarm is triggered
Light control
Select whether the light should be controlled by
a door switch, a day/night signal or by a signal
via data communication
Light at Main SW = Off
Choose whether the light is to be switched off
when the main switch is set to off, or if the light
is to follow the standard light control.
Control of Blinds control
Set whether the blinds are to be controlled by
a relay.
Open/close blinds via DI
Set whether the controller is to receive a signal
which activates the blinds. This must be a pulse
signal.
Forced closing via DI
Select whether a digital input is used for the
forced closing of injection
Fan at forced closing
Select whether or not you want the fans to oper-
ate during forced closing.
Alarm relay
Select the alarm relay function.
The alarm relay must be activated by alarm
priorities:
• low to high
• low to medium
• high
The alarm relay can be activated either by all
alarm priorities from low to high or only by high
priority alarms
Ext. main switch
Select whether you want a main switch via a
digital input. When the main switch is set to Off,
all regulation is stopped, all outputs are set to
standby and all alarms are cancelled.