AFD/VFG(S) 2(1)

ENGLISH

Safety Notes

Prior to assembly and commissioning 
to avoid injury of persons and 
damages of the devices, it is 

absolutely necessary to carefully read and 
observe these instructions.

Necessary assembly, start-up, and maintenance 
work must be performed only by qualified, 
trained and authorized personnel. 

Prior to assembly and maintenance work on the 
controller, the system must be:

- depressurized, 
- cooled down,
- emptied and 
- cleaned.

Please comply with the instructions of the 
system manufacturer or system operator.

Definition of Application

The controller is used for pressure reduction 
of steam, water and water glycol mixtures for 
heating, district heating and cooling systems. 
The technical data on the label plates determine 
the use.

Scope of Delivery 

-  control valve VFG 2(1)/VFGS2
-  extension piece ZF4 for DN < 150  

if T

max

 > 200 °C

-  actuator AFD
-  flow divider FD for steam noise reduction 
-  seal pot V1, V2 if T > 150 °C
-  impulse tubes AF

Mounting

 

Only for VFGS 2 valves: 

If ordered, install flow divider cage. 
Read installation Instructions 

 

attached to the flow divider cage.

Admissible Installation Positions 

DN 15-80 media temperatures up to 120 °C:

Can be installed in any position.

DN 100-250 and DN 15-80, media 
temperatures higher >120 °C and always at 
steam:

Installation only permitted in horizontal 
pipelines with the actuator hanging 
downwards.

Installation Scheme 

 

Note:

The valve is open without pressure and 

is closing on rising pressure.

System must be protected behind the 
pressure reducer by a safety 
monitoring unit (SV, SÜV) 

.

Valve Installation 

1.  Install strainer 

 

 before the controller.

2.  Rinse system prior to installing the valve.
3.  Observe flow direction 

 on the valve body.

 Flanges 

 in the pipeline must be in 

parallel position and sealing surfaces 
must be clean and without any 
damage.

4.  Install the valve.
5.  Tighten screws crosswise in 3 steps up to the 

max. torque.

Valve Actuator Installation 

Only for valves

VFGS2 DN 15-125; T = 200-350 °C:

Install stem extension ZF4.

Read Installation Instructions attached to the 
stem extension 

.

Valves DN 150‑250

The actuator stem must be screwed 
into the valve stem.

Observe the Installation Instructions for the DN 
150 - 250 valves 

.

1. Place the actuator stem to the valve stem 

and screw together gently by hand until it 
stops. Rotate the nut simultaneously - makes 
it easier 

.

2.  Unscrew for approximately one turn.
3.  Tighten union nut 

 

Torque 100 Nm

Valves DN 15‑125

1.  Screw the actuator nut to the valve neck 

2.  Align actuator, observe position of impulse 

tube connection 

.

3.  Tighten union nut 

 

Torque 100 Nm

Impulse Tube Installation 

 

Note: 

When installing seal pots 

, please 

observe the Installation Instructions for the 
seal pots.

Which impulse tubes to use?

Use the impulse tube set AF (1×) 

Order No.: 

003G1391

 

or use the following pipes:

Stainless steel

Ø 10×0.8

DIN 17458
DIN 2391

Steel

Ø 10×1

DIN 2391

Copper

Ø 10×1

DIN 1754

The impulse tube 

 can be connected directly 

to the valve 

④ 

or to the pipeline 

.

 ventilation socket, do not connect 

impulse tube.

Connection to the valve 

1.  Remove plug 

 at the valve (return side).

2.  Screw in threaded joint G 1/4 

 with copper 

seal, Torque 40 Nm.

- or -

Connection to the Pipeline 

 

No connection downwards/upwards 

, could 

bring dirt/air into an impulse tube.
1.  Cut pipe in rectangular sections 

 and 

deburr.

2.  For copper pipe:  

insert sockets 

 on both sides.

3.   Verify the correct position of the cutting 

ring 

.

4.  Press impulse tube 

 into the threaded joint 

up to its stop.

5.  Tighten union nut 

 Torque 40 Nm.

Insulation 

For media temperatures up to 100 °C the 
pressure actuator 

 may be insulated.

Dismounting 

Danger 
Danger of injury by steam, hot 
water!

Valve without actuator is open 

, seal 

 is in 

the actuator.
Prior to dismounting, depressurize system!

Carry out dismounting in reverse order to 
mounting.

Leak and Pressure Tests 

Observe max. permitted pressure, see 
below.

The pressure 

 behind the valve must not 

exceed the pressure 

 before the valve.

Non compliance may cause damages at the
controller 

.

Prior the pressure tests

, it is 

absolutely

 

necessary to disconnect the impulse tube 

.

Close connections with a plug e.g. G 1/4 ISO 228.

Max. pressure [bar] with connected impulse 
tube

AFD cm

2

32

80

160

250

630

bar

16

6

1.5

0.5

Observe nominal pressure 

 of the valve.

Max. test pressure is 1.5 × PN

.

Filling the System, First Start‑up 

The pressure 

 behind the valve must 

not exceed the pressure 

 before the 

valve.

Non-compliance may cause damages at the 
controller 

.

1.  Open shut-off units 

 at the impulse tube, if 

any.

2.  Slowly open shut-off unit 

 (inlet).

3.  Slowly open shut-off unit 

 (outlet).

4.  Only for actuator 630 cm²:  

Open ventilation screw 

 by about 2 turns. 

As soon as water is penetrating, close screw.

Putting out of Operation 

1.  Slowly close shut-off units 

 (inlet).

2.  Slowly close shut-off units 

 (outlet).

Setpoint Adjustment 

Set-point range see rating plate 

.

1.  Adjust flow rate at a fitting 

 after the 

pressure reducer 

 to about 50 % of the 

max. flow rate 

.

2.  Adjustment of the 

pressure behind the 

valve

 

Turning to the right 

 increases the 

set-point (stressing the spring, tension 
spring) 
Turning to the left 

 reduces the set-point 

(unstressing the spring)

3.  The set-point adjuster 

 may be sealed.

Dimensions, Weights 

Содержание AFD

Страница 1: ...FD VFG S 2 1 www danfoss com Page 6 DEUTSCH Druckminderer AFD VFG S 2 1 www danfoss de Seite 7 FRANCAIS D tendeur AFD VFG S 2 1 www danfoss fr Page 8 SVENSKA Tryckreducerare AFD VFG S 2 1 www danfoss...

Страница 2: ...15 125 Tmax 200 C DN 15 125 Tmax 350 C DN 150 250 Tmax 200 C DN 150 250 Tmax 350 C VFG 2 1 VFG 2 1 VFG 2 VFGS 2 VFG 2 VFGS 2 ZF4 AFD AFD AFD AFD AFD AFD 1 1 1 1 V1 V2 630 cm2 V1 V2 630 cm2 V1 V2 630 c...

Страница 3: ...Danfoss 2021 05 3 AQ13418645844301 010402 AFD VFG S 2 1 G 1 4 AF ZF4 DN 150 250 SW 13 40 Nm SW 19 100 Nm SW 46 40 Nm SW 19...

Страница 4: ...01 010402 4 Danfoss 2021 05 AFD VFG S 2 1 EN GJL 250 GG 25 VFG VFGS PN 16 VFG PN 25 EN GJS 400 GGG 40 3 VFG PN 40 EN GP 240 GH GS C 25 EN GJS 400 GGG 40 3 VFGS PN 25 EN GP 240 GH GS C 25 VFGS PN 40 10...

Страница 5: ...V1 298 140 Seal pot V2 Valve stem extension D40 155 Valve stem extension ZF4 ZF5 180 95 Valve stem extension ZF6 SW 36 VFG 2 VFG 21 VFGS 2 Valves DN 15 20 25 32 40 50 65 80 100 125 150 200 250 L mm 1...

Страница 6: ...2 Align actuator observe position of impulse tube connection 3 Tighten union nut Torque 100 Nm Impulse Tube Installation Note When installing seal pots please observe the Installation Instructions fo...

Страница 7: ...rieb wegen dem Steuerleitungsanschluss ausrichten 3 berwurfmutter anziehen Anzugsmoment 100 Nm Montage Steuerleitungen Hinweis Bei Einbau von Vorlagegef en bitte den Vorlagegef en bei gef gte Montagea...

Страница 8: ...m Vannes DN 15 125 1 Visser l crou de l actionneur sur le col de la vanne 2 Aligner le moteur avec le raccordement de conduite de commande 3 Serrer l crou prisonnier facteur de serrage 100 Nm Montage...

Страница 9: ...Reglerdelensspindelskruvasi ventilensspindel Observera monteringsanvisningarna f r ventiler DN 150 250 1 Placera st lldonsaxeln p ventilaxeln och skruva ihop f rsiktigt f r hand tills det tar stopp V...

Страница 10: ...C Zamontowa przed u k trzpienia ZF4 Przeczyta instrukcj monta u do czon do przed u enia trzpienia Zawory DN 150 250 WzaworachDN150 250trzpie nap dumusizosta wkr conyw trzpie zaworu Szczeg y znale mo n...

Страница 11: ...esp odcinaj cy wylot Regulacja nastawy Zakres nastawy jest widoczny na p ytce 1 Ustawi przep yw na z czce za reduktorem ci nienia na oko o 50 przep ywu maksymalnego 2 Dokona regulacji ci nienia za zaw...

Страница 12: ...2 3 4 630 cm 2 1 2 1 50 2 3 VFG 2 1 VFGS 2 ZF4 DN 150 Tmax 200 C AFD FD V1 V2 T 150 C AF VFGS2 DN 15 80 120 C DN 100 250 DN 15 80 120 C SV S V 1 2 3 4 5 VFGS 2 DN 15 125 T 200 350 C ZF4 DN 150 250 DN...

Страница 13: ...Danfoss 2021 05 13 AQ13418645844301 010402 AFD VFG S 2 1 4 5 40 Nm 100 C G 1 4 ISO 228 bar AFD cm2 32 80 160 250 630 bar 16 6 1 5 0 5 1 5 PN 1 2 3 4 630 cm 2 1 2 1 50 2 3...

Страница 14: ...AQ13418645844301 010402 14 Danfoss 2021 05 AFD VFG S 2 1...

Страница 15: ...Danfoss 2021 05 15 AQ13418645844301 010402 AFD VFG S 2 1...

Страница 16: ...73696420 AQ13418645844301 010402 16 Danfoss DCS S SI 2021 05 AFD VFG S 2 1...

Отзывы: