IOM 1274-3 • CENTRIFUGAL WATER CHILLERS 62 www.DaikinApplied.com
Operation
Controller Inputs and Outputs
As outlined below, inputs and outputs vary between the unit controller and the compressor controller.
Unit Controller Inputs and Outputs
The following tables list the unit controller inputs and outputs, both analog and digital, as well as the stepper motor outputs.
Table 24: Unit Controller, Analog Inputs
Description
Wiring
Source
Signal
Sensor Range
2
Entering Evaporator Water Temperature
Chiller
NTC Thermistor
10k @ 25°C
-40 to 125°C
Leaving Evaporator Water Temperature
1
Chiller
NTC Thermistor
10k @ 25°C
-40 to 125°C
Entering Condenser Water Temperature
Chiller
NTC Thermistor
10k @ 25°C
-40 to 125°C
Leaving Condenser Water Temperature
Chiller
NTC Thermistor
10k @ 25°C
-40 to 125°C
Liquid Line Refrigerant Temperature
Chiller
NTC Thermistor
10k @ 25°C
-40 to 125°C
Evaporator Water Flow Rate
Field
Water Flow Sensor
4 to 20 mA Current
0 to 10,000 gpm
Condenser Water Flow Rate
Field
Water Flow Sensor
4 to 20 mA Current
0 to 10,000 gpm
Reset of Leaving Water Temperature
Field
BAS
4 to 20 mA Current
0 to 100%
Demand Limit
Field
BAS
4 to 20 mA Current
0 to 100%
Entering Heat Recovery Temp
Chiller
NTC Thermistor
10k @ 25°C
-40 to 125°C
Leaving Heat Recovery Temperature
Chiller
NTC Thermistor
10k @ 25°C
-40 to 125°C
NOTE:
1. Wiring is to the compressor box.
2. “Sensor Range” in
Table 24
indicates the range of the input, NOT the operating range of the chiller.
Table 25: Unit Controller, Digital Inputs
Description
Wiring
Signal Source
States (Open / Closed)
Front Panel “Stop/Auto” Unit Switch
Chiller
Isolated Switch Contacts
Stop / Auto
Remote Start/Stop
Field
Isolated Switch or Relay Contacts
Stop / Start
Mode Switch
Chiller
Isolated Switch Contacts
Cool / Ice or Heat
Table 26: Unit Controller, Analog Outputs
Description
Signal
Sensor Range
Cooling Tower Bypass Valve Position
0 to 10 VDC
0 to 100% Open
Cooling Tower VFD Speed
0 to 10 VDC
0 to 100%
Electronic Expansion Valve
0 to 10 VDC
0 to 100% Open
NOTE:
“Sensor Range” in
Table 26
indicates the range of the output, NOT the operating range of the chiller.
Table 27: Unit Controller, Digital Outputs
Description
Source
Rating
Alarm
Indicator Light
120 VAC
Evaporator Water Pump #1
Pump Contactor
240 VAC
Evaporator Water Pump #2
Pump Contactor
240 VAC
Condenser Water Pump #1
Pump Contactor
240 VAC
Condenser Water Pump #2
Pump Contactor
240 VAC
Cooling Tower Fan #1
Fan Contactor
240 VAC
Cooling Tower Fan #2
Fan Contactor
240 VAC
Cooling Tower Fan #3
Fan Contactor
240 VAC
Cooling Tower Fan #4
Fan Contactor
240 VAC
Содержание WSC
Страница 4: ......
Страница 21: ...Installation www DaikinApplied com 21 IOM 1274 3 CENTRIFUGAL WATER CHILLERS Figure 17 Compressor Control Box ...
Страница 22: ...IOM 1274 3 CENTRIFUGAL WATER CHILLERS 22 www DaikinApplied com Installation Figure 18 Unit Control Box ...
Страница 73: ... www DaikinApplied com 73 IOM 1274 3 CENTRIFUGAL WATER CHILLERS ...
Страница 74: ...IOM 1274 3 CENTRIFUGAL WATER CHILLERS 74 www DaikinApplied com ...