IOM 1274-3 • CENTRIFUGAL WATER CHILLERS 48 www.DaikinApplied.com
Operation
Figure 54: Settings View - Modes
Table 14: Modes Setpoints
Description
Default
Range
PW
Comments
Chiller Model
WCF
WCF, WMC
T
WCF is the general software model for WSC (HSC), WDC, WCC, TSC,
and TDC. Heat Recovery option is enabled on Commission tab shown in
Figure 72 on page 57
.
WCC Enable
Disabled (other)
Enabled (WCC), Disabled (other) T
Will always be Disabled for WSC chillers
Control Source
Switches
Switches, Local, Network BAS
O
Sets control source. See
“Unit Enabling/Disabling” on page 36
.
Unit Enable
OFF
OFF, AUTO
O
OFF: everything is off. AUTO: evap pump on, comp, cond pump and tower on
as required to meet LWT
Available Modes
Cool/Heat
Cool Only, Cool w/ Glycol, Cool/
Ice w/ Glycol, Ice Only w/ Glycol,
Cool/Heat, Heat Only
M
See Water Setpoints,
Figure 52
, for control temperature targets for each mode
No. of Compressors
1
1 to 2
T
WSC models will be set to 1. Any other value will be ignored.
Max Compressors On
2
0 to 8
M
Max number of compressors that can be on local pLan chiller network
HATS - Starting
Off
Off, Chiller, System
M
High Ambient Tandem Start
Condenser Pump
Pump #1 Only
Pump #1 Only, Pump #2 Only,
Auto Lead, #1 Primary, #2
Primary
M
Pump #1 Only, Pump #2 Only, use only these pumps AUTO, balance hours
between #1 and #2 #1 Primary, #2 Primary, if primary fails, use other
Evaporator Pump
Pump #1 Only
Pump #1 Only, Pump #2 Only,
Auto Lead, #1 Primary, #2
Primary
M
Pump #1 Only, Pump #2 Only, use only these pumps AUTO, balance hours
between #1 and #2 #1 Primary, #2 Primary, if primary fails, use other
Stage Mode
Normal
Normal, Hi Eff, Pump, Standby
M
Normal - Fixed sequence and /or balance starts/hours.
Hi Eff - Starts compressor on each dual compressor chiller first
Pump - Starts all compressors on one chiller first.
Standby - Use compressor only if another fails.
Stage Sequence
1
0-99
M
Sets fixed sequence for compressor staging
Hot Gas Mode
RLA
Off, Water, RLA
T
See below
Hot Gas Control Point
20%
20 to 70%
T
Sets hot gas control point %
Available Modes
In “Switches Control” mode, the choices with the “/” require
the Mode Switch to be closed. The alternate mode to the right
of the “/” will require the mode switch when this mode is the
current operating mode.
“BAS Network Control” mode does not need the mode switch
to run alternate modes.
Heat makes a unit operate as a Templifier unit and Ice makes
the unit run for ice making applications.
Hot Gas (HG) Mode
Water
- proportionally opens an HG valve as the ELWT drops
below the ELWT setpoint, it is fully open 0.5°F above shutdown
ELWT.
RLA
- proportionally opens an HG valve as the amps drop
below the HG setpoint, the solenoid valve will open in unison
with the proportional valve. The valve will close as the %RLA
exceeds the setpoint by 5%.
Содержание WSC
Страница 4: ......
Страница 21: ...Installation www DaikinApplied com 21 IOM 1274 3 CENTRIFUGAL WATER CHILLERS Figure 17 Compressor Control Box ...
Страница 22: ...IOM 1274 3 CENTRIFUGAL WATER CHILLERS 22 www DaikinApplied com Installation Figure 18 Unit Control Box ...
Страница 73: ... www DaikinApplied com 73 IOM 1274 3 CENTRIFUGAL WATER CHILLERS ...
Страница 74: ...IOM 1274 3 CENTRIFUGAL WATER CHILLERS 74 www DaikinApplied com ...