Operation
www.DaikinApplied.com 55
IOM 1274-3 • CENTRIFUGAL WATER CHILLERS
Figure 68: Settings View - Alarms
Table 17: ALARMS Setpoint Settings
Description
Default
Range
PW
Comments
Condenser Freeze Protect
34.0 °F
-9.0 to 45.0 °F
T
Sets the value of condenser saturated temperature below which the condenser pump is forced
ON - occurs when unit is off and chiller senses need to provide flow to address a chiller limit
alarm - see
“Table 23: Warning Alarms and Informative Messages” on page 61
Evaporator Freeze Protect
34.0 °F
-9.0 to 45.0 °F
T
Sets the value of evaporator saturated temperature below which the evaporator pump is
forced ON - occurs when unit is off and chiller senses need to provide flow to address a chiller
limit alarm - see
“Table 23: Warning Alarms and Informative Messages” on page 61
.
High Condenser Pressure
140 psi
120 to 270 psi
T
Sets the condenser pressure above which the compressor is shut down.
High Discharge Temp - Load
170 °F
120 to 240 °F
T
Discharge temp above which a forced capacity increase occurs.
High Discharge Temp - Stop
190 °F
120 to 240 °F
T
Discharge temp above which the compressor is shut down.
Low Suction Pressure - Inhibit
33 psi
7 to 45 psi
T
Sets the evaporator pressure value below which any capacity increase is inhibited - may need
to be lowered if glycol is added to the system. Similarly, changing setpoint below 30 psi default
requires glycol to be added to the system otherwise there is a risk of freezing the evaporator.
Low Suction Pressure - Unload 31 psi
6 to 45 psi
T
Suction pressure value below which a forced capacity decrease occurs.
Low Suction Pressure - Stop
29 psi
5 to 45 psi
T
Suction pressure value below which compressor is shut down.
Motor Current Threshold
10%
3 to 99%
T
When % RLA is below setpoint, motor is considered OFF.
Surge Temp Limit
6 °F
2 to 25 °F
T
Surge Temp (ST) = Suction Temp - Evap Leaving Temp, ST is compared to SP.
If LESS, alarm occurs when ST > 2x setpoint.
If MORE, slope alarm is active until ST < this setpoint, then alarm at 2x setpoint.
Surge Slope Limit
20 °F/min 1 to 99 °F/min
T
Sets Surge Temp Slope above which alarm occurs.
Lenient Flow Sensing
Off
Off, On
T
When ON, allows the chiller to run without flow as long as the unit does not approach an
alarm. When OFF, a trip timer for each vessel will determine timing allowed before issuing a
flow loss alarm.
High Oil Feed Temp
140 °F
120 to 240 °F
T
Above limit, compressor shuts down.
Low Oil Delta Temp
30 °F
20 to 80 °F
T
Delta Temp (above evaporator saturated temp); If value is below setpoint, compressor shuts
down.
Low Net Oil Pressure
50 psi
0 to 90 psi
T
Net Oil Pressure (Feed pressure - sump pressure); If value is below setpoint, compressor
shuts down.
Содержание WSC
Страница 4: ......
Страница 21: ...Installation www DaikinApplied com 21 IOM 1274 3 CENTRIFUGAL WATER CHILLERS Figure 17 Compressor Control Box ...
Страница 22: ...IOM 1274 3 CENTRIFUGAL WATER CHILLERS 22 www DaikinApplied com Installation Figure 18 Unit Control Box ...
Страница 73: ... www DaikinApplied com 73 IOM 1274 3 CENTRIFUGAL WATER CHILLERS ...
Страница 74: ...IOM 1274 3 CENTRIFUGAL WATER CHILLERS 74 www DaikinApplied com ...