IOM 1274-3 • CENTRIFUGAL WATER CHILLERS 60 www.DaikinApplied.com
Operation
Table 22: Critical Alarms
Screen Text
Action Taken
Troubleshooting
Clear
Evaporator Pressure Low
Rapid Stop
Low or No Evaporator Water Flow. Low refrigerant level in evaporator. Incorrect setpoint value for
leaving water temperature.
Manual
Discharge Pressure High
Rapid Stop
Low or no condenser water Flow
Manual
Vanes Not Closed
Rapid Stop
Manual
Oil Pressure Low
Rapid Stop
Manual
Oil Feed Temperature Low
Rapid Stop
Manual
Oil Feed Temperature High
Rapid Stop
Manual
RLA Low (motor open)
Rapid Stop
Manual
Discharge Temperature High
Rapid Stop
Low or no condenser water Flow
Manual
High Pressure Switch
Rapid Stop
Manual
Motor Temperature High
Rapid Stop
Rotor and/or stator cooling circuit fault
Motor stator cooling solenoid not open, rotor cooling stepper motor not functioning correctly,
motor rotor superheat or gain setpoints incorrect (contact factory)
Manual
Surge Detected - Running
Rapid Stop
Surge Temperature = the suction temperature minus the leaving chilled water temperature.
Manual
Surge Condition
Rapid Stop/No Start
Surge condition detected while starting
Manual
No Starter Transition
Rapid Stop/No Start
Manual
Starter Fault
Rapid Stop
Manual
Prelube Cycle Failed
Rapid Stop/No Start
Oil pressure too low to start compressor.
Manual
Evaporator Water Flow Loss
Rapid Stop
Loss of evaporator flow, evaporator pump off, evaporator head gasket leaking or missing, sensor
wiring fault, evaporator flow sensor failure
Manual
Condenser Water Flow Loss
Rapid Stop
Loss of condenser flow, condenser pump off, condenser head gasket leaking or missing, sensor
wiring fault, condenser flow sensor failure
Manual
Sensor Fault: Evap LWT
Rapid Stop
Sensor shorted or open. Chilled water flow switch may be open
Manual
Sensor Fault: Evap Sat Press
Rapid Stop/No Start
Sensor shorted or open. Check for loose wires or failed sensor
Manual
Sensor Fault: Cond Sat Press
Rapid Stop/No Start
Sensor shorted or open. Check for loose wires or failed sensor
Manual
Sensor Fault: Suction Temp
Rapid Stop/No Start
Sensor shorted or open. Check for loose wires or failed sensor
Manual
Sensor Fault: Discharge Temp
Rapid Stop/No Start
Sensor shorted or open. Check for loose wires or failed sensor
Manual
Sensor Fault: Oil Feed Temp
Rapid Stop/No Start
Sensor shorted or open. Check for loose wires or failed sensor
Manual
Sensor Fault: Oil Sump Temp
Rapid Stop/No Start
Sensor shorted or open. Check for loose wires or failed sensor
Manual
Sensor Fault: Oil Feed Pressure Rapid Stop/No Start
Sensor shorted or open. Check for loose wires or failed sensor
Manual
Sensor Fault: Oil Vent Pressure Rapid Stop/No Start
Sensor shorted or open. Check for loose wires or failed sensor
Manual
External Input Comp Fault
Rapid Stop
Manual
Starter Current Overload
Rapid Stop
Manual
Starter Current Imbalance
Rapid Stop
Manual
Starter Phase Loss
Rapid Stop
Manual
Starter Phase Order
Rapid Stop
Manual
Starter Over Volt
Rapid Stop
Manual
Starter Under Volt
Rapid Stop
Manual
Ground Fault
Rapid Stop
Manual
Sensor Fault: Leaving Heat
Recovery
Rapid Stop
Manual
External Fault Digital Input
Rapid Stop
Manual
Motor Temperature Trip - NTC
Rapid Stop
Manual
Motor Temperature Trip - DI
Rapid Stop
Manual
IGV Actuator Fault
Rapid Stop
Manual
IGV Position Tracking Error
Rapid Stop
Manual
Содержание WSC
Страница 4: ......
Страница 21: ...Installation www DaikinApplied com 21 IOM 1274 3 CENTRIFUGAL WATER CHILLERS Figure 17 Compressor Control Box ...
Страница 22: ...IOM 1274 3 CENTRIFUGAL WATER CHILLERS 22 www DaikinApplied com Installation Figure 18 Unit Control Box ...
Страница 73: ... www DaikinApplied com 73 IOM 1274 3 CENTRIFUGAL WATER CHILLERS ...
Страница 74: ...IOM 1274 3 CENTRIFUGAL WATER CHILLERS 74 www DaikinApplied com ...