SiUS331604E
Outline of Control (Indoor Unit)
Functions and Control
54
6.2.2 With the Optional Infrared Floor Sensor
The relationship between remote controller set temperature and control target temperature is described below.
•
The temperature difference for cooling
⇔
heating mode switching is 5°C (9°F).
•
When using the floor temperature as the control target, the remote controller set temperature is equal to the
actual control target temperature in heating operation.
•
The above also applies to automatic operation.
When setting the suction air thermistor (Default setting)
When using the remote controller thermistor (Field setting is required)
Examples are given to illustrate a control target temperature that satisfies the remote controller set temperature.
Regarding control target temperature
When using the infrared floor sensor, the temperature around people will be treated as the control target
temperature for operation.
What is the temperature around people?
The temperature around people refers to the temperature of the living space, obtained from the temperature
around the ceiling and the temperature underfoot. The temperature is calculated using the detected values of the
suction air thermistor and the infrared floor sensor.
It is difficult to use only suction air temperature control for underfoot air conditioning.
˚C
Remote controller set temperature
Control target temperature
Remote controller set temperature
Control target temperature
Cooling
Heating
˚F
Temperature
Remote controller set temperature
Control target temperature
Remote controller set temperature
Control target temperature
Cooling
Heating
˚C
˚F
Temperature
Содержание VRV IV-S RXTQ-TAVJU Series
Страница 1: ...Service Manual SiUS331604E RXTQ36 48 60TAVJU Heat Pump 60 Hz...
Страница 253: ...SiUS331604E Wiring Diagrams Appendix 240 1 Wiring Diagrams 1 1 Outdoor Unit RXTQ36TAVJU 3D100495A...
Страница 254: ...Wiring Diagrams SiUS331604E 241 Appendix RXTQ48TAVJU 3D100496A...
Страница 255: ...SiUS331604E Wiring Diagrams Appendix 242 RXTQ60TAVJU 3D100497A...
Страница 260: ...Wiring Diagrams SiUS331604E 247 Appendix FXEQ07 09 12 15 18 24PVJU C 3D098557...
Страница 267: ...SiUS331604E Wiring Diagrams Appendix 254 FXTQ12 18 24 30 36 42 48 54PAVJU 3D065036G...
Страница 269: ...SiUS331604E Wiring Diagrams Appendix 256 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269C...
Страница 270: ...Wiring Diagrams SiUS331604E 257 Appendix VAM1200GVJU 3D073270C...
Страница 271: ...Revision History Month Year Version Revised contents 06 2016 SiUS331604E First edition...