SiUS331604E
Troubleshooting by Error Code
Service Diagnosis
150
4.9
Electronic Expansion Valve Coil Abnormality, Dust
Clogging
Error Code
A9
Applicable
Models
All indoor units
Method of Error
Detection
Electronic expansion valve coil conditions are checked via micro-computer.
The electronic expansion valve main body is checked for dust clogging via micro-computer.
Error Decision
Conditions
Pin input for electronic expansion valve coil is abnormal when initializing micro-computer.
Either of the following conditions is seen/caused/occurs while the unit stops operation.
z
Temperature of suction air (R1T) – temperature of liquid pipe of heat exchanger (R2T) > 8°C
(14.4°F).
z
Temperature of liquid pipe of heat exchanger (R2T) shows fixed degrees or below.
Supposed
Causes
Defective electronic expansion valve coil
Defective indoor unit main PCB
Defective relay cables
Содержание VRV IV-S RXTQ-TAVJU Series
Страница 1: ...Service Manual SiUS331604E RXTQ36 48 60TAVJU Heat Pump 60 Hz...
Страница 253: ...SiUS331604E Wiring Diagrams Appendix 240 1 Wiring Diagrams 1 1 Outdoor Unit RXTQ36TAVJU 3D100495A...
Страница 254: ...Wiring Diagrams SiUS331604E 241 Appendix RXTQ48TAVJU 3D100496A...
Страница 255: ...SiUS331604E Wiring Diagrams Appendix 242 RXTQ60TAVJU 3D100497A...
Страница 260: ...Wiring Diagrams SiUS331604E 247 Appendix FXEQ07 09 12 15 18 24PVJU C 3D098557...
Страница 267: ...SiUS331604E Wiring Diagrams Appendix 254 FXTQ12 18 24 30 36 42 48 54PAVJU 3D065036G...
Страница 269: ...SiUS331604E Wiring Diagrams Appendix 256 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269C...
Страница 270: ...Wiring Diagrams SiUS331604E 257 Appendix VAM1200GVJU 3D073270C...
Страница 271: ...Revision History Month Year Version Revised contents 06 2016 SiUS331604E First edition...