Troubleshooting by Error Code
SiUS331604E
139
Service Diagnosis
4.4
Indoor Fan Motor (M1F) Lock, Overload
Error Code
A6
Applicable
Models
FXFQ, FXUQ, FXEQ, FXMQ07-12PB, FXAQ
Method of Error
Detection
Abnormal fan revolutions are detected by a signal output from the fan motor.
Error Decision
Conditions
When the fan revolutions do not increase
Supposed
Causes
Broken wires in, short circuit of, or disconnection of connectors from the fan motor harness
Defective fan motor
(Broken wires or defective insulation)
Abnormal signal output from the fan motor (defective circuit)
Defective indoor unit main PCB
Instantaneous disturbance in the power supply voltage
Fan motor lock
(Due to motor or external causes)
The fan does not rotate due to foreign matter blocking the fan.
Disconnection of the connector between the high-power PCB (A1P) and the low-power PCB
(A2P) (FXMQ07-12PB only)
Содержание VRV IV-S RXTQ-TAVJU Series
Страница 1: ...Service Manual SiUS331604E RXTQ36 48 60TAVJU Heat Pump 60 Hz...
Страница 253: ...SiUS331604E Wiring Diagrams Appendix 240 1 Wiring Diagrams 1 1 Outdoor Unit RXTQ36TAVJU 3D100495A...
Страница 254: ...Wiring Diagrams SiUS331604E 241 Appendix RXTQ48TAVJU 3D100496A...
Страница 255: ...SiUS331604E Wiring Diagrams Appendix 242 RXTQ60TAVJU 3D100497A...
Страница 260: ...Wiring Diagrams SiUS331604E 247 Appendix FXEQ07 09 12 15 18 24PVJU C 3D098557...
Страница 267: ...SiUS331604E Wiring Diagrams Appendix 254 FXTQ12 18 24 30 36 42 48 54PAVJU 3D065036G...
Страница 269: ...SiUS331604E Wiring Diagrams Appendix 256 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269C...
Страница 270: ...Wiring Diagrams SiUS331604E 257 Appendix VAM1200GVJU 3D073270C...
Страница 271: ...Revision History Month Year Version Revised contents 06 2016 SiUS331604E First edition...