Troubleshooting by Error Code
SiUS331604E
213
Service Diagnosis
Troubleshooting
NO
NO
YES
Not available for combined use with
remote control adaptor. Dismount
the remote control adaptor, and
then reset the power supply of all
the centralized controllers.
Not available for combined
use of schedule timer and
Master Station III. Dismount
either, and then reset all the
centralized controllers.
Not available for combined
use of schedule timer and
DMF-IF. Dismount either,
and then reset all the
centralized controllers.
Dismount the Independent/Combined
use connector of the schedule timer,
and then reset all the centralized
controllers.
Integrate one unit for the
centralized controller
connected with the
connector, and then reset all
the centralized controllers.
Disconnect the setting connector of the
master centralized controller and connect
it to a different centralized controller, and
then reset the power supply of all the
centralized controllers. If after this the
error is resolved, the centralized controller
connected with the setting connector is
faulty. Replace the controller.
YES
YES
Does the
schedule timer
connect?
NO
NO
NO
NO
Does the
Master Station III
connect?
YES
NO
Does the DMF-IF
connect?
YES
NO
Does the parallel
interface connect?
YES
YES
YES
Centralized controller: Normal
Master unit centralized
connector setting table
CHECK 14
Not available for combined
use of schedule timer and
parallel interface. Dismount
either, and then reset all the
centralized controllers.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
The remote
control adaptor (KRP2A series)
is connected.
Does the
Independent/Combined
use connector (CN1/X1A) of the
schedule timer connect?
Are
there two or
more centralized
controllers connected with
setting connectors
(CN1/X1A)?
Possibly caused by external
factors (such as interference)
related to other equipment.
Reset the
power supply of all the
centralized controllers.
MA
error recurs?
CHECK 14
Содержание VRV IV-S RXTQ-TAVJU Series
Страница 1: ...Service Manual SiUS331604E RXTQ36 48 60TAVJU Heat Pump 60 Hz...
Страница 253: ...SiUS331604E Wiring Diagrams Appendix 240 1 Wiring Diagrams 1 1 Outdoor Unit RXTQ36TAVJU 3D100495A...
Страница 254: ...Wiring Diagrams SiUS331604E 241 Appendix RXTQ48TAVJU 3D100496A...
Страница 255: ...SiUS331604E Wiring Diagrams Appendix 242 RXTQ60TAVJU 3D100497A...
Страница 260: ...Wiring Diagrams SiUS331604E 247 Appendix FXEQ07 09 12 15 18 24PVJU C 3D098557...
Страница 267: ...SiUS331604E Wiring Diagrams Appendix 254 FXTQ12 18 24 30 36 42 48 54PAVJU 3D065036G...
Страница 269: ...SiUS331604E Wiring Diagrams Appendix 256 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269C...
Страница 270: ...Wiring Diagrams SiUS331604E 257 Appendix VAM1200GVJU 3D073270C...
Страница 271: ...Revision History Month Year Version Revised contents 06 2016 SiUS331604E First edition...