Outline of Control (Indoor Unit)
SiUS372201EB
183
Part 4 Functions and Control
Note(s)
9.3 Remote Controller Thermistor
Temperature is controlled by both the remote controller thermistor and suction air thermistor for the
indoor unit. (This is however limited to when the field setting for the remote controller thermistor is
set to Use.)
When fresh air intake kit is used, outdoor air is mixed with indoor air, and the room temperature
may not reach the set temperature, since TS and TH1 do not enter the area in which remote
controller thermistor can be used. In such case, install the remote sensor (optional accessory) in
your room, and set the field settings to not use the remote controller thermistor.
FXTQ-TA, FXTQ-TB, and CXTQ-TA models do not have this control because they do not have
suction air thermistor. The thermistor is selectable manually when remote sensor (optional
accessory) is installed.
Cooling
If there is a significant difference in the set temperature and the suction temperature, fine
adjustment control is carried out using a suction air thermistor, or using the remote controller
thermistor near the position of the user when the suction temperature is near the set temperature.
Assuming the set temperature in the figure above is 24
C (75
F), and the suction
temperature has changed from 18
C (64
F) to 30
C (86
F) (A
F):
(This example also assumes there are several other air conditioners, and the suction temperature
changes even when the thermostat is off.)
Suction air thermistor is used for temperatures from 18°C (64°F) to 23°C (73°F) (A
C).
Remote controller thermistor is used for temperatures from 23°C (73°F) to 27°C (81°F) (C
E).
Suction air thermistor is used for temperatures from 27°C (81°F) to 30°C (86°F) (E
F).
Range in
w
hich remote controller
thermistor can
b
e
u
sed
Range in
w
hich
s
u
ction air thermistor
can
b
e
u
sed
Differential
Set temperat
u
re (Ts)
12
14
16
18
20
22
24
26
28
30
32
34
53.6
57.2
60.8
64.4
68.0
71.6
75.2
78.8
82.4
86.0
89.6
93.2
°
C
°
F
°
C
32
30
28
26
24
22
20
18
16
°
F
89.6
86.0
82.4
78.8
75.2
71.6
68.0
64.4
60.8
TH1 = Ts + 1 (
°
C)
TH1 = Ts + 1.8 (
°
F)
TH1 = Ts + 3 (
°
C)
TH1 = Ts + 5.4 (
°
F)
TH1 = Ts – 3 (
°
C)
TH1 = Ts – 5.4 (
°
F)
TH1 = Ts – 1 (
°
C)
TH1 = Ts – 1.8 (
°
F)
S
u
ction air temperat
u
re (TH1)
Содержание VRV EMERION REYQ-AATJA
Страница 1: ...Service Manual Heat Recovery 60 Hz REYQ AATJA B 208 230 V REYQ AAYDA B 460 V SiUS372201EB...
Страница 458: ...Check SiUS372201EB 451 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 457 CHECK 8 Refer to page 458...
Страница 490: ...Wiring Diagrams SiUS372201EB 483 Part 7 Appendix 1 2 2 Multi Branch Selector Unit Standard Series BS4Q54TVJ 3D089123B...
Страница 492: ...Wiring Diagrams SiUS372201EB 485 Part 7 Appendix BS6 8Q54TVJ 2D089122B...
Страница 493: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 486 BS10 12Q54TVJ 2D089121B...
Страница 499: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 492 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 500: ...Wiring Diagrams SiUS372201EB 493 Part 7 Appendix BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 501: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 494 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 505: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 498 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 506: ...Wiring Diagrams SiUS372201EB 499 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 507: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 500 FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU C 3D110467C...
Страница 509: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 502 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 513: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 506 FXHQ12 24 36MVJU 3D048116C...
Страница 514: ...Wiring Diagrams SiUS372201EB 507 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 521: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 514 VAM1200GVJU 3D073270D...