AlertMaxx

Installation & Operating Instructions

For Ground Water (DMS - 270) and Foul Water (DMS - 269)

T. 

01992 523532

E. [email protected]

W. www.deltamembranes.com

Pump Station High Level Alarm

Содержание AlertMaxx DMS-269

Страница 1: ...AlertMaxx Installation Operating Instructions For Ground Water DMS 270 and Foul Water DMS 269 T 01992 523532 E info deltamembranes com W www deltamembranes com Pump Station High Level Alarm...

Страница 2: ...AlertMaxx...

Страница 3: ...axx unit 6 7 0 Installing the float switch in the chamber 7 7 1 Installing a finger float into a ground or surface water chamber 7 7 2 Installing a pendant float into a foul water chamber 7 8 0 Connec...

Страница 4: ...4 For technical support please call 01279 757400 AlertMaxx Groundwater version DMS 270 1 x Finger Float Switch 1 x Finger Float Housing 2 x Cable Ties Foul Water version DMS 269 1 x Pendant Float Swit...

Страница 5: ...Mounting instructions 5 1 Mounting the AlertMaxx unit 1 Using the template provided on page 15 of this instruction manual figure 1 mark the fixing positions on the wall 2 Drill the two holes and fit...

Страница 6: ...rom a qualified electrician Figure 2 Connecting mains E N L 7 0 Installing the float switch in the chamber Care must be taken to ensure the correct type of float switch is installed into the chamber F...

Страница 7: ...ttom of the float switch to hang approximately 350mm above the base of the chamber see figure 7 Suitable for ground surface water Suitable for foul water E N L Option 2 Guide rail mounted foul pump 1...

Страница 8: ...in the chamber 8 For technical support please call 01279 757400 AlertMaxx Figure 6 Ground Water Sump DMS 164 Figure 5 Ground Water Float Switch Figure 7 Foul Water Sump DMS 165 Figure 8 Foul Water Flo...

Страница 9: ...he small cable gland When using the pendant float switch figure 4 use the large cable gland 3 Connect the float switch cable to the terminal strip When using the finger float figure 3 connect the blue...

Страница 10: ...8 0 Connecting the float switch to the AlertMaxx unit 10 For technical support please call 01279 757400 AlertMaxx Figure 10 Wiring a pendant float switch BLUE BLACK...

Страница 11: ...three times 4 Check that the green LED flashes every second and after one minute the unit emits a short beep followed by a flash from the red LED every 5 seconds 5 Turn on the mains power supply to th...

Страница 12: ...rnal devices such as an alarm or beacon When the alarm is activated the relay sends a signal once every second The volt free relay is designed to accept devices with a maximum load of 0 5A and voltage...

Страница 13: ...ET button However the beep will return 7 days from pressing the RESET button until a service technician resets the alarm unit The AlertMaxx unit has a factory default service interval of 12 months 12...

Страница 14: ...arge the battery by connecting mains supply to alarm unit Still doesn t turn on after 3 mins alarm unit is faulty The LEDs flash in the following order red blue green Low battery charge the battery by...

Страница 15: ...AlertMaxx For technical support please call 01279 757400 15 Figure 1 Scale 1 1 Mounting hole positions Top Bottom...