SiUS372201EB
Field Setting from Outdoor Unit
Part 5 Field Settings and Test Operation
252
90
Indoor unit
without power
Multi-tenant function setting
2.
9
0
Invalid
Valid (No U4 error generation)
Valid (Operating with U4
warning)
0
1
2
92
Te target
temperature
upper limit
Used to make setting of targeted
evaporating temperature upper
limit for cooling and heat recovery
operation.
2.
9
2
L
M
H
0
1
2
97
Auxiliary heater
maximum
allowable
temperature
Auxiliary heater is allowed to
energize when the ambient
temperature is smaller than the
auxiliary heater maximum
allowable temperature.
2.
9
7
–17.7°C (0°F)
–15°C (5°F)
–12.2°C (10°F)
–9.4°C (15°F)
–6.6°C (20°F)
–3.8°C (25°F)
–1.1°C (30°F)
1.6°C (35°F)
4.4°C (40°F)
7.2°C (45°F)
10°C (50°F)
12.7°C (55°F)
15.5°C (60°F)
18.3°C (65°F)
Auxiliary heater always not
allowed
Auxiliary heater always
allowed
1
1
1
1
1
1
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
98
Auxiliary heater
maximum
allowable
temperature
release
differential
Auxiliary heater is not allowed to
energize when the outdoor air
temperature is recovered by
differential above the auxiliary
heater maximum allowable
temperature.
2.
9
8
2.8°C (5°F)
5.6°C (10°F)
8.3°C (15°F)
0
1
2
No.
1
Item
Description
7 segment
display
Description
7 segment
display
Range
SEG
1
SEG
2
SEG
3
SEG
1
SEG
2
SEG
3
1: Numbers in the
No.
column represent the number of times to press the BS button.
: Setting does not return to factory setting when exit mode 2. To cancel the function, change
setting manually to factory setting.
: Once function is activated
t01
appears. To stop current function, press once the
RETURN
(BS3)
button. For detailed description about each setting, refer to
Details of Setting Mode 2
on page 253.
Indication
bold
means factory setting.
Содержание VRV EMERION REYQ-AATJA
Страница 1: ...Service Manual Heat Recovery 60 Hz REYQ AATJA B 208 230 V REYQ AAYDA B 460 V SiUS372201EB...
Страница 458: ...Check SiUS372201EB 451 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 457 CHECK 8 Refer to page 458...
Страница 490: ...Wiring Diagrams SiUS372201EB 483 Part 7 Appendix 1 2 2 Multi Branch Selector Unit Standard Series BS4Q54TVJ 3D089123B...
Страница 492: ...Wiring Diagrams SiUS372201EB 485 Part 7 Appendix BS6 8Q54TVJ 2D089122B...
Страница 493: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 486 BS10 12Q54TVJ 2D089121B...
Страница 499: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 492 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 500: ...Wiring Diagrams SiUS372201EB 493 Part 7 Appendix BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 501: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 494 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 505: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 498 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 506: ...Wiring Diagrams SiUS372201EB 499 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 507: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 500 FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU C 3D110467C...
Страница 509: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 502 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 513: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 506 FXHQ12 24 36MVJU 3D048116C...
Страница 514: ...Wiring Diagrams SiUS372201EB 507 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 521: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 514 VAM1200GVJU 3D073270D...