SiUS372201EB
Refrigerant Circuit (Piping Diagrams)
Part 2 Refrigerant Circuit
64
1.1.3 REYQ192/216/240AA
No. in
piping
diagram
Electric
symbol
Name
Function
(1)
M1C
Compressor 1
Compressor is operated in multi-steps according to Te and Tc.
(2)
M2C
Compressor 2
(3)
M1F
Fan motor 1
The fan rotation speed is varied by using inverter.
(4)
M2F
Fan motor 2
(5)
Y1E
Electronic expansion valve
(Heat exchanger right upper)
While being used as evaporator, PI control is applied to keep the outlet
superheating degree of air heat exchanger constant.
(6)
Y2E
Electronic expansion valve
(Heat exchanger right lower)
(7)
Y3E
Electronic expansion valve
(Subcooling heat exchanger)
PI control is applied to keep the outlet superheating degree of subcooling
heat exchanger constant.
(8)
Y4E
Electronic expansion valve
(Receiver gas purge)
Used to collect the refrigerant to receiver.
(9)
Y5E
Electronic expansion valve
(Heat exchanger left)
While being used as evaporator, PI control is applied to keep the outlet
superheating degree of air heat exchanger constant.
(10)
Y6E
Electronic expansion valve
(Refrigerant cooling IPM)
Used to control the refrigerant flow to cool the diode bridge and power
module of the inverter PCB.
(11)
Y7E
Electronic expansion valve
(Refrigerant cooling air)
Used to control the refrigerant flow to cool the air inside the electrical
component box.
(12)
Y8E
Electronic expansion valve
Not used
(13)
Y1S
Solenoid valve
(Oil separator oil return 2)
Used to return oil from the oil separator to the compressor.
(14)
Y2S
Solenoid valve
(Oil separator oil return 1)
(15)
Y3S
Solenoid valve (Liquid shutoff)
Used to shut off liquid refrigerant flow to the receiver.
(16)
Y4S
Solenoid valve
(Accumulator oil return)
Used to return oil from the accumulator to the compressor.
(17)
Y5S
Solenoid valve
(Refrigerant adjustment)
Not used
(18)
Y6S
Solenoid valve (Injection)
Used to control compressor injection.
(19)
Y7S
Four way valve
(Heat exchanger right lower)
Used to switch outdoor heat exchanger to evaporator or condenser.
(20)
Y8S
Four way valve
(HP/LP gas pipe)
Used to switch dual pressure gas pipe to high pressure or low pressure.
(21)
Y9S
Four way valve
(Heat exchanger left)
Used to switch outdoor heat exchanger to evaporator or condenser.
(22)
Y10S Four way valve
(Heat exchanger right upper)
(23)
Y11S Solenoid valve
(Refrigerant cooling bypass)
Used when Y6E alone does not provide enough cooling.
(24)
S1NPH High pressure sensor
Used to detect the high pressure.
(25)
S1NPL Low pressure sensor
Used to detect the low pressure.
(26)
S1PH High pressure switch
This functions when pressure increases to stop operation and avoid high
pressure increase in the fault operation.
(27)
S2PH High pressure switch
(28)
—
Pressure regulating valve
(Liquid pipe)
This is used when pressure increases, to prevent any damage on
components caused by pressure increase in transport or storage.
(29)
—
Subcooling heat exchanger
Apply subcooling to liquid refrigerant.
(30)
—
Capillary tube
Used to return the refrigerating oil separated through the oil separator to the
compressor.
(31)
—
Capillary tube
(32)
R1T
Thermistor (Outdoor air)
Used to detect outdoor air temperature, correct discharge pipe temperature
and for other purposes.
(33)
R2T
Thermistor
(Heat exchanger right upper gas
pipe)
This detects temperature of gas pipe for air heat exchanger.
(34)
R3T
Thermistor
(Electrical box air outlet)
Used to detect the outlet pipe temperature of refrigerant cooling air.
(35)
R4T
Thermistor
(Receiver gas purge)
Used to detect gas pipe temperature of receiver gas purge piping.
Содержание VRV EMERION REYQ-AATJA
Страница 1: ...Service Manual Heat Recovery 60 Hz REYQ AATJA B 208 230 V REYQ AAYDA B 460 V SiUS372201EB...
Страница 458: ...Check SiUS372201EB 451 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 457 CHECK 8 Refer to page 458...
Страница 490: ...Wiring Diagrams SiUS372201EB 483 Part 7 Appendix 1 2 2 Multi Branch Selector Unit Standard Series BS4Q54TVJ 3D089123B...
Страница 492: ...Wiring Diagrams SiUS372201EB 485 Part 7 Appendix BS6 8Q54TVJ 2D089122B...
Страница 493: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 486 BS10 12Q54TVJ 2D089121B...
Страница 499: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 492 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 500: ...Wiring Diagrams SiUS372201EB 493 Part 7 Appendix BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 501: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 494 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 505: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 498 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 506: ...Wiring Diagrams SiUS372201EB 499 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 507: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 500 FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU C 3D110467C...
Страница 509: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 502 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 513: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 506 FXHQ12 24 36MVJU 3D048116C...
Страница 514: ...Wiring Diagrams SiUS372201EB 507 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 521: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 514 VAM1200GVJU 3D073270D...