Check
SiUS372201EB
475
Part 6 Service Diagnosis
Warning
Warning
Electrical Checks - High Voltage Power Circuits
HIGH VOLTAGE!
Disconnect ALL power before servicing or installing. Multiple power sources may be present.
Failure to do so may cause property damage, personal injury or death.
Line Voltage now present.
8.
The green LED on the diagnostic tool will blink indicating communications between the
tool and motor. See table below for indications of tool indicators and motor actions.
Replace or repair as needed.
Power
Button
Green
LED
Motor
Action
Indication(s)
OFF
OFF
Not
Rotating
Confirm 24VAC to UltraCheck-EZ
TM
tool. If 24VAC
is confirmed, diagnostic tool is inoperable.
ON
Blinking
Rotating
Motor and control/end bell are functioning properly.
ON
OFF
Rotating
Replace motor control/end bell.
ON
Blinking
Not
Rotating
Check motor (refer to Motor Checks on page 477).
ON
OFF
Not
Rotating
Replace motor control/end bell; verify motor (refer to
Motor Checks on page 477).
9.
Depress the orange power button to turn off motor.
10. Disconnect power. Disconnect diagnostic tool.
11. Reconnect the 4-wire harness from control board to motor.
1.
Disconnect power to air handler or modular blower.
2.
Disconnect the 5-circuit power connector to the ECM motor.
3.
Turn on power to air handler or modular.
4.
Measure voltage between pins 4 and 5 on the 5-circuit connector. Measured voltage
should be the same as the supply voltage to the air handler or modular.
5.
Measure voltage between pins 4 and 3. Voltage should be approximately half of the
voltage measured in step 4.
6.
Measure voltage between pins 5 and 3. Voltage should be approximately half of the
voltage measured in step 4.
7.
If no voltage is present, check supply voltage to air handler or modular blower.
8.
Disconnect power to air handler or modular blower. Reconnect the 5-circuit power
harness disconnected in step 2.
1
2
3
4
5
Lines 1 and 2 will be connected
for 120VAC Power Connector
applications only
Gnd
AC Line Connection
AC Line Connection
}
Содержание VRV EMERION REYQ-AATJA
Страница 1: ...Service Manual Heat Recovery 60 Hz REYQ AATJA B 208 230 V REYQ AAYDA B 460 V SiUS372201EB...
Страница 458: ...Check SiUS372201EB 451 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 457 CHECK 8 Refer to page 458...
Страница 490: ...Wiring Diagrams SiUS372201EB 483 Part 7 Appendix 1 2 2 Multi Branch Selector Unit Standard Series BS4Q54TVJ 3D089123B...
Страница 492: ...Wiring Diagrams SiUS372201EB 485 Part 7 Appendix BS6 8Q54TVJ 2D089122B...
Страница 493: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 486 BS10 12Q54TVJ 2D089121B...
Страница 499: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 492 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 500: ...Wiring Diagrams SiUS372201EB 493 Part 7 Appendix BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 501: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 494 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 505: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 498 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 506: ...Wiring Diagrams SiUS372201EB 499 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 507: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 500 FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU C 3D110467C...
Страница 509: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 502 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 513: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 506 FXHQ12 24 36MVJU 3D048116C...
Страница 514: ...Wiring Diagrams SiUS372201EB 507 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 521: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 514 VAM1200GVJU 3D073270D...