Unit installation
Installer and user reference guide
68
RXYSA4~6A7V/Y1B
VRV 5-S system air conditioner
4P600330-1 – 2020.01
The outdoor unit is designed for outdoor installation only, and for the following
ambient temperatures:
Heating
–20~21°C DB
–20~15.5°C WB
Cooling
–5~46°C DB
Note:
For indoor installation of the outdoor unit, check the applicable legislation.
NOTICE
The equipment described in this manual may cause electronic noise generated from
radio-frequency energy. The equipment complies to specifications that are designed
to provide reasonable protection against such interference. However, there is no
guarantee that interference will not occur in a particular installation.
It is therefore recommended to install the equipment and electric wires in such a
way that they keep a proper distance from stereo equipment, personal computers,
etc.
b
b
c
c
f
e
a d
(mm)
≥
1500
≥
1500
≥
1500
≥
1000
≥
1000
≥
1000
≥
1000
≥
1000
≥
1000
d
a
Personal computer or radio
b
Fuse
c
Earth leakage protector
d
User interface
e
Indoor unit
f
Outdoor unit
▪
In places with weak reception, keep distances of 3 m or more to avoid
electromagnetic disturbance of other equipment and use conduit tubes for
power and transmission lines.
▪
Select a place where rain can be avoided as much as possible.
▪
Take care that in the event of a water leak, water cannot cause any damage to
the installation space and surroundings.
▪
Choose a location where the operation noise or the hot/cold air discharged from
the unit will not disturb anyone.
▪
Heat exchanger fins are sharp and injury is possible. Choose an installation
location where there is no risk for injury (especially in areas where children play).
Do NOT install the unit in the following places:
▪
Sound sensitive areas (e.g. near a bedroom), so that the operation noise will
cause no trouble.
Note: If the sound is measured under actual installation conditions, the
measured value might be higher than the sound pressure level mentioned in
Sound spectrum in the data book due to environmental noise and sound
reflections.
INFORMATION
The sound pressure level is less than 70 dBA.
▪
In places where a mineral oil mist, spray or vapour may be present in the
atmosphere. Plastic parts may deteriorate and fall off or cause water leakage.