22
|
Configuration
Installer and user reference guide
124
RXYSA4~6A7V/Y1B
VRV 5-S system air conditioner
4P600330-1 – 2020.01
[2‑9]
T
c
target temperature during heating operation.
[2‑9]
T
c
target (°C)
0 (default)
Auto
1
41
3
43
6
46
For more information and advice about the impact of these settings, see
"22.3 Energy saving and optimum operation"
[2‑12]
Enable the low noise function and/or power consumption limitation via external
control adaptor (DTA104A61/62).
If the system needs to be running under low noise operation or under power
consumption limitation conditions when an external signal is sent to the unit, this
setting should be changed. This setting will only be effective when the optional
external control adaptor (DTA104A61/62) is installed.
[2‑12]
Description
0 (default)
Deactivated.
1
Activated.
[2‑18]
Fan high static pressure setting.
If the static pressure of the the outdoor unit fan increases, the airflow decreases
and the fan motor power input increases. The unit is able to estimate the ESP via
measurements.
Via this setting, the installer can set the ESP to a fixed level or change the moment
of ESP evaluation.
Note:
For an ESP level higher than 45 Pa, level 0 is kept for reliability of the fan
motor.
[2‑18]
High ESP setting
0 (default)
Auto setting at commissioning mode and stand-by mode
1
Auto setting at commissioning mode only
2
Level 0 (ESP between 0-20 Pa)
3
Level 1 (ESP between 20-35 Pa)
4
Level 2 (ESP between 35-45 Pa)
[2‑20]
Manual additional refrigerant charge.
[2‑20]
Description
0 (default)
Deactivated.