20
|
Electrical installation
Installer and user reference guide
103
RXYSA4~6A7V/Y1B
VRV 5-S system air conditioner
4P600330-1 – 2020.01
Transmission wiring specification and limits
(a)
Maximum wiring length
(distance between outdoor and furthest indoor unit)
300 m
Total wiring length
(sum of distances between outdoor and all indoor units)
600 m
(a)
If the total transmission wiring exceeds these limits, communication errors might occur.
No secondary branchings are allowed after any transmission wire branching.
A
B
C
b2
b3
c1
c2
b1
a
A
Outdoor unit
B
Indoor unit
C
Central user interface (etc...)
a
Main line
b1, b2, b3
Branch lines
c1, c2
No branch is allowed after branch
Example:
e
d
F1/F2
(16 V)
F1/F2
(16 V)
220-240 V
1~ 50 Hz
c
a
Y
V
b
220-240 V
1~ 50 Hz
380-415 V
3N~ 50 Hz
a
Main switch
b
Earth connection
c
Power supply wiring (including earth) (EMC shielded cable)
F1/F2
Transmission wiring (EMC shielded cable)
V
Outdoor unit (RXYSA4~6_V)
Y
Outdoor unit (RXYSA4~6_Y)
d
Indoor unit
e
User interface