Domestic hot water tank for Daikin Altherma Monobloc (R32)

 

 

 

Switch box

 

Carry out a thorough visual inspection of the switch box and look for obvious 
defects such as loose connections or defective wiring.

 

Check for correct operation of contactor K3M by use of an ohmmeter. All 
contacts of this contactor must be in open position.

 

Pressure relief valve hose

 

Check the condition and routing of the hose. Water must drain appropriately 
from the hose.

 

Booster heater of the domestic hot water tank

 

It is recommended to remove lime build up on the booster heater to extend its 
life span, especially in regions with hard water. To do so, drain the domestic hot 
water tank, remove the booster heater from the domestic hot water tank and 
immerse in a bucket (or similar) with lime

-

removing product for 24 hours.

 

10

 

Troubleshooting

 

10.1

 

Overview: Troubleshooting

 

This chapter describes what you have to do in case of problems. It contains 
information about solving problems based off symptoms.

 

Before troubleshooting

 

Carry out a thorough visual inspection of the unit and look for obvious defects 
such as loose connections or defective wiring.

 

10.2

 

Precautions and troubleshooting

 

DANGER: RISK OF ELECTROCUTION

 

DANGER: RISK OF BURNING

 

WARNING

 

When carrying out an inspection o the switch box of the unit, AL-
WAYS make sure that the unit is disconnected from the mains. Turn 
off the respective circuit breaker.

 

When a safety device was activated, stop the unit and find out why 
the safety device was activated before resetting it. NEVER bridge 
safety devices or change their values to a value other than the 
factory default setting. If you are unable to find the cause of the 
problem, call your dealer.

 

WARNING

 

Prevent hazards due to inadvertent resetting of the thermal cut

-

out: this appliance MUST NOT be supplied through an external 
switching device, such as a timer, or connected to a circuit that is 
regularly turned ON and OFF by the utility

 

10.3

 

Solving problems based on symptoms

 

10.3.1

 

Symptom: No water flow from hot taps

 

Possible causes

 

Corrective action

 

The main water supply is OFF

 

The cold water inlet pressure reducing 
valve is not fitted properly.

 

The strainer is blocked.

 

Turn OFF the water supply, remove 
and clean the strainer of the Inlet 
control group (field supply).

 

The cold water inlet pressure reducing 
valve is not fitted properly. 

 

Check and refit as required.

 

10.3.2

 

Symptom: The water from the hot taps is cold

 

Possible causes

 

Corrective action

 

The thermal cut

-

out(s) has/have oper-

ated.

 

Check and reset the button(s)

 

The unit is NOT operating.

 

Check unit operation. Refer to the 
manual delivered with the unit. If any 
faults are suspected, contact your 
dealer.

 

10.3.3

 

Symptom: Intermittent water discharge

 

Possible causes

 

Corrective action

 

Thermal control failure (water will be 
hot).

 

• 

Turn OFF the power to the unit.

 

• 

When discharge has stopped, check 
the thermal controls and replace if 
faulty.

 

• 

Contact your local dealer.

 

The expansion vessel is broken.

 

Replace the expansion vessel.

 

10.3.4

 

Symptom: Continuous water discharge

 

Possible causes

 

Corrective action

 

Cold water inlet pressure.

 

Check the pressure reducing valve. 
Replace the pressure reducing valve if 
the measured pressure is >2.1 bar

 

Temperature and pressure relief valve.

 

Check and reset button.

 

The expansion relief valve is not 
functioning properly

 

Check for correct operation of the 
pressure relief valve by turning the red 
knob on the valve counter clockwise:

 

• 

If your do not hear a clacking sound, 
contact your local dealer.

 

• 

In case the water keeps running out 
of the unit, close both the water 
inlet and outlet shut

-

off valves first 

and then contact your local dealer.

 

11

 

Disposal

 

NOTICE

 

Do NOT try to dismantle the system yourself: dismantling the of the 
system, treatment of the refrigerant, oil and other parts MUST 
comply with applicable legislation. Units MUST be treated at a 
specialised treatment facility for reuse, recycling and recovery.

 

Содержание UK.PPC150SL/R32

Страница 1: ...Altherma R32 Monobloc Systems Installation Manual UK PPC150SL R32 UK PPC150 R32 UK PPC180SL R32 UK PPC180 R32 UK PPC210 R32 UK PPC250 R32 UK PPC300 R32 English Installation Manual Domestic hot water...

Страница 2: ...that nobody especially children can play with them Possible risk suffocation DANGER RISK OF BURNING Do NOT touch the refrigerant piping water piping or internal parts during and immediate after operat...

Страница 3: ...rical DANGER RISK OF ELECTROCUTION Turn OFF all power supply before removing the switch box cover connecting electrical wiring or touching electrical parts Disconnect the power supply for more than 1...

Страница 4: ...5 consecutive days after installation Domestic hot water tank Standstills In cases where during longer periods of time there is no consumption of hot water the equipment MUST be flushed with fresh wa...

Страница 5: ...mponents The discharge pipe away from the tundish must terminate in a safe visible position without forming any risk to persons in the vicinity WARNING Do NOT install any valves between the domestic h...

Страница 6: ...must be installed by a qualified electrician The fuse rating should be sized correctly to suite the heater s duty and isolators must be double pole to BS 3456 Correct cable sizing must be carried out...

Страница 7: ...4 5 5 Parts List 4 5 6 Plan View and Dimensions Allow 300mm space in front for servicing immersion heater...

Страница 8: ...the factory the pre plumbed cylinder will be supplied with the vessel as a hydraulic separator In order to change the vessel to function only as a volumiser use the following configuration NOTICE On B...

Страница 9: ...d protection devices are installed according to this document and have not been bypassed There are NO loose connections or damaged electrical components in the switch box The immersion heater circuit...

Страница 10: ...tic cover of the pressure reducing valve 2 Extract the cartridge with the aid of long nosed pliers to grip the heat of the set screw 3 Remove the strainer element 4 Clean the strainer element and cart...

Страница 11: ...device such as a timer or connected to a circuit that is regularly turned ON and OFF by the utility 10 3 Solving problems based on symptoms 10 3 1 Symptom No water flow from hot taps Possible causes C...

Страница 12: ...the Dixell control panel We recommend the setpoint to be 37o C however it could be changed based on your requirements e g if using low temperature heat emitters If there is no possibility for water ci...

Страница 13: ...UK PPC150 300 SL R32 November 2022 Version 2 1 Domestic hot water tank for Daikin Altherma Monobloc R32 12 Technical data 12 1 Components Domestic hot water tank 12 2 Exploded Diagram...

Страница 14: ...eight kg 46 56 59 71 86 Material inside cylinder Stainless steel 2304 Water inlet H E mm 28 Piping connections diameter Water outlet H E mm 28 Cold water in mm 22 Hot water out mm 22 Domestic hot wate...

Страница 15: ...and applicable for a certain product or domain Service company Qualified company which can perform or coordinate the require service to the product Accessories Labels manuals information sheets and eq...

Страница 16: ...Appendix Wiring Connections Factory Fitted Wiring Wiring when using Madoka BRC1HHD Controller...

Страница 17: ...Third Party Thermostat 1 Zone Wiring when using Third Party Thermostat 2 Zones Third party controller must be volt free and TPI disabled Cable must be sized for 230V Third party controller must be vol...

Страница 18: ...and Service Record Log Book CUSTOMER DETAILS NAME ADDRESS TEL No IMPORTANT 1 Please keep the Log Book in a safe place for future reference 2 This Log Book is to be completed in full by the competent p...

Страница 19: ...VALVE AND EXPANSION VALVE FITTED AND DISCHARGE TESTED YES NO IS PRIMARY ENERGY SOURCE CUT OUT FITTED NORMALLY 2 PORT VALVE YES NO WHAT IS THE PRESSURE REDUCING VALVE SETTING IF FITTED YES NO WHERE IS...

Страница 20: ...ENTS SIGNATURE SERVICE 2 DATE ENGINEER NAME COMPANY NAME TEL No COMMENTS SIGNATURE SERVICE 3 DATE ENGINEER NAME COMPANY NAME TEL No COMMENTS SIGNATURE SERVICE 4 DATE ENGINEER NAME COMPANY NAME TEL No...

Страница 21: ...UK PPC150 300 SL R32 November 2022 Version 2 1 Domestic hot water tank for Daikin Altherma Monobloc R32...

Страница 22: ...Daikin UK 1 The Heights Brooklands Weybridge Surrey KT13 0NY...

Отзывы: