background image

 

UK.PPC150

-

300(SL)/R32

 

 

November 

2022

—Version 2.1

 

Domestic hot water tank for Daikin Altherma Monobloc (R32)

 

 

 

DANGER: RISK OF ELECTROCUTION

 

DANGER: RISK OF BURNING

 

WARNING

 

• 

Before carrying out any maintenance or repair activity, ALWAYS 
switch off the circuit breaker on the supply panel, remove the 
fuses or open the protection devices of the unit.

 

• 

Make sure you do NOT touch a conductive section.

 

• 

Do NOT rinse the outside of the unit. This may cause electric 
shocks or fire.

 

NOTICE: Risk of electrostatic discharge

 

Before performing any maintenance or service work, touch a metal 
part of the unit in order to eliminate static electricity and to protect 
the PCB

 

7.1

 

Draining the cylinder

 

Before draining the cylinder, the immersion heater should be isolated to 
prevent the element from burning out. Shut the cold feed ball valve to isolate 
the cylinder from the cold feed. Securely connect a hose pipe to the drain 
connection on the cylinder and take to a nearby waste or soak

-

away. The drain 

point should be below the level of the cylinder to ensure that the maximum 
amount of water is drained from the cylinder. The nearest hot tap should be 
opened to allow air back into the system and prevent a vacuum being pulled in 
the cylinder. Care must be taken as the draining water may be hot.

 

7.2

 

Annual maintenance

 

Check the following at least once a year:

 

• 

Temperature and pressure relief valve

 

• 

Inlet control group

 

• 

Relief valve of the domestic hot water tank

 

• 

Descaling

 

• 

Chemical disinfection

 

• 

Switch box

 

• 

Pressure relief valve hose

 

• 

Immersion heater of the domestic hot water tank

 

Temperature and pressure relief valve

 

Check the correct operation of the temperature and pressure relief valve. 
Manually operate the temperature and pressure relief valve to ensure free 
water flow through the discharge pipe. Turn knob left.

 

Inlet control group

 

The inlet control group is a pressure reducing valve with integrated non

-

return 

valve and line strainer. Depending on local water conditions, annual inspection 
of the integral line strainer, pressure reducing valve cartridge and seating may 
be necessary.

 

A)

 

Cartridge

 

B)

 

Strainer

 

C)

 

Calibration screw

 

 

1.

 

Unscrew the plastic cover of the pressure reducing valve.

 

2.

 

Extract the cartridge with the aid of long nosed pliers to grip the heat 
of the set screw.

 

3.

 

Remove the strainer element.

 

4.

 

Clean the strainer element and cartridge under clean running water

 

5.

 

Replace if the strainer or cartridge are damaged.

 

6.

 

Refit the strainer, cartridge and cover.

 

7.

 

If the cartridge has been replaced, calibrate the pressure reducing 
valve.

 

• 

Close the downstream isolating valve (field supply).

 

• 

Install a hex key on the calibration screw in the centre of the plastic cover. 
Rotate it clockwise to increase the outlet pressure and anticlockwise to 
reduce it.

 

Relief valve of the domestic hot water tank (field supply).

 

Open the valve and check the correct operation. 

Water may be very hot!

 

Checkpoints are:

 

• 

The water flow coming from the relief valve are high enough, no blockage of 
the valve or in between piping is suspected.

 

• 

Dirty water coming out of the relief valve.

 

• 

Open the valve until the discharged water does not contain dirt 
anymore.

 

• 

Flush and clean the complete tank, including the piping between the 
relief valve and cold water inlet.

 

To make sure this water originates from the tank, check after a tank heat up 
cycle.

 

It is recommended to do this maintenance more frequently.

 

Descaling

 

Depending on water quality and set temperature, scale can deposit on the heat 
exchanger inside the domestic hot water tank and can restrict heat transfer. For 
this reason, descaling of the heat exchanger may be require at certain intervals.

 

Chemical disinfection

 

If the applicable legislation requires a chemical disinfection in specific 
situations, involving the domestic hot water tank, please be aware that the 
domestic hot water tank is a stainless steel cylinder containing an aluminium 
anode. We recommend to use a non

-

chloride based disinfection approved for 

use with water intended for human consumption.

 

NOTICE

 

When using means for descaling or chemical disinfection, it must be 
ensured that the water quality remains compliant with EU directive 
98/83 EC.

 

This chapter contains information about:

 

• 

the yearly maintenance of the domestic hot water tank.

 

NOTICE

 

Maintenance MUST be done by an authorized installer or service 
agent.

 

We recommend performing maintenance at least once a year. 
However, applicable legislation might require shorter maintenance 
intervals.

 

7

 

Maintenance and service

 

Содержание UK.PPC150SL/R32

Страница 1: ...Altherma R32 Monobloc Systems Installation Manual UK PPC150SL R32 UK PPC150 R32 UK PPC180SL R32 UK PPC180 R32 UK PPC210 R32 UK PPC250 R32 UK PPC300 R32 English Installation Manual Domestic hot water...

Страница 2: ...that nobody especially children can play with them Possible risk suffocation DANGER RISK OF BURNING Do NOT touch the refrigerant piping water piping or internal parts during and immediate after operat...

Страница 3: ...rical DANGER RISK OF ELECTROCUTION Turn OFF all power supply before removing the switch box cover connecting electrical wiring or touching electrical parts Disconnect the power supply for more than 1...

Страница 4: ...5 consecutive days after installation Domestic hot water tank Standstills In cases where during longer periods of time there is no consumption of hot water the equipment MUST be flushed with fresh wa...

Страница 5: ...mponents The discharge pipe away from the tundish must terminate in a safe visible position without forming any risk to persons in the vicinity WARNING Do NOT install any valves between the domestic h...

Страница 6: ...must be installed by a qualified electrician The fuse rating should be sized correctly to suite the heater s duty and isolators must be double pole to BS 3456 Correct cable sizing must be carried out...

Страница 7: ...4 5 5 Parts List 4 5 6 Plan View and Dimensions Allow 300mm space in front for servicing immersion heater...

Страница 8: ...the factory the pre plumbed cylinder will be supplied with the vessel as a hydraulic separator In order to change the vessel to function only as a volumiser use the following configuration NOTICE On B...

Страница 9: ...d protection devices are installed according to this document and have not been bypassed There are NO loose connections or damaged electrical components in the switch box The immersion heater circuit...

Страница 10: ...tic cover of the pressure reducing valve 2 Extract the cartridge with the aid of long nosed pliers to grip the heat of the set screw 3 Remove the strainer element 4 Clean the strainer element and cart...

Страница 11: ...device such as a timer or connected to a circuit that is regularly turned ON and OFF by the utility 10 3 Solving problems based on symptoms 10 3 1 Symptom No water flow from hot taps Possible causes C...

Страница 12: ...the Dixell control panel We recommend the setpoint to be 37o C however it could be changed based on your requirements e g if using low temperature heat emitters If there is no possibility for water ci...

Страница 13: ...UK PPC150 300 SL R32 November 2022 Version 2 1 Domestic hot water tank for Daikin Altherma Monobloc R32 12 Technical data 12 1 Components Domestic hot water tank 12 2 Exploded Diagram...

Страница 14: ...eight kg 46 56 59 71 86 Material inside cylinder Stainless steel 2304 Water inlet H E mm 28 Piping connections diameter Water outlet H E mm 28 Cold water in mm 22 Hot water out mm 22 Domestic hot wate...

Страница 15: ...and applicable for a certain product or domain Service company Qualified company which can perform or coordinate the require service to the product Accessories Labels manuals information sheets and eq...

Страница 16: ...Appendix Wiring Connections Factory Fitted Wiring Wiring when using Madoka BRC1HHD Controller...

Страница 17: ...Third Party Thermostat 1 Zone Wiring when using Third Party Thermostat 2 Zones Third party controller must be volt free and TPI disabled Cable must be sized for 230V Third party controller must be vol...

Страница 18: ...and Service Record Log Book CUSTOMER DETAILS NAME ADDRESS TEL No IMPORTANT 1 Please keep the Log Book in a safe place for future reference 2 This Log Book is to be completed in full by the competent p...

Страница 19: ...VALVE AND EXPANSION VALVE FITTED AND DISCHARGE TESTED YES NO IS PRIMARY ENERGY SOURCE CUT OUT FITTED NORMALLY 2 PORT VALVE YES NO WHAT IS THE PRESSURE REDUCING VALVE SETTING IF FITTED YES NO WHERE IS...

Страница 20: ...ENTS SIGNATURE SERVICE 2 DATE ENGINEER NAME COMPANY NAME TEL No COMMENTS SIGNATURE SERVICE 3 DATE ENGINEER NAME COMPANY NAME TEL No COMMENTS SIGNATURE SERVICE 4 DATE ENGINEER NAME COMPANY NAME TEL No...

Страница 21: ...UK PPC150 300 SL R32 November 2022 Version 2 1 Domestic hot water tank for Daikin Altherma Monobloc R32...

Страница 22: ...Daikin UK 1 The Heights Brooklands Weybridge Surrey KT13 0NY...

Отзывы: