Components
Service manual
51
ATXP20~35 + FTXP20~71 + ARXP20~35 + RXP20~71
Split Comfora R32
ESIE18-01C – 2020.07
a
a
a
a
Faston connector
4
Cut the compressor pipes (below the soldered joint) using a pipe cutter.
a
a
a
Compressor pipe
5
Supply nitrogen to the refrigerant circuit. The nitrogen pressure MUST NOT
exceed 0.02 MPa.
6
Heat the ends of the compressor pipes using an oxygen acetylene torch and
remove the compressor pipe ends.
7
Stop the nitrogen supply when the piping has cooled down.
8
Remove the all the nuts and remove the compressor from the unit.