2
|
Components
Service manual
89
ATXP20~35 + FTXP20~71 + ARXP20~35 + RXP20~71
Split Comfora R32
ESIE18-01C – 2020.07
VDC
Comm
Resistance
VDC
Comm
Resistance
4
3
1.2 kΩ
3
4
1.2 kΩ
4
7
OL
7
4
OL
INFORMATION
The measured resistance values may deviate from the listed values due to instability
during the measurements.
DC fan motor resistance measurements
are correct?
Action
Yes
Continue with the next step.
No
Replace the DC fan motor, see
6
Turn ON the power of the unit.
7
With the DC fan motor connector S71 disconnected from the inverter PCB,
measure the voltage on the connector pins 4-7 (= fan motor power supply) on
the inverter PCB.
Result:
The voltage MUST be 200~390 V DC.
8
Measure the voltage on the connector pins 4-3 (= fan motor control) on the
inverter PCB.
Result:
The voltage MUST be 15±10% V DC.
Are both measured voltages correct?
Action
Yes
Continue with the next step.
No
Perform a check of the inverter PCB,
see
9
Measure the voltage on the DC fan motor connector S71 pins 2-4 (= rotation
command) on the PCB.
Result:
The measured voltage should be 0~7 V DC. It should NOT be 0 V DC.
Is the measured voltage 0 V DC?
Action
Yes
Perform a check of the inverter PCB, see
73].
No
Continue with the next step.
10
Manually (slowly) rotate the fan blade propeller 1 turn and measure the
voltage on the DC fan motor connector pins 1-4. 4 pulses MUST be measured.
Pulses are measured during fan blade
propeller rotation?
Action
Yes
Perform a check of the main PCB, see
No
Problem solved?
After all checking procedures listed above have been performed:
Содержание Split Comfora R32