Service Manual SM-Inverter_(i)
14
OVERALL CURRENT CONTROL
-
To monitor the overall current and to restrict the compressor upper limit rotation in order to prevent
circuit breakers from exceeding the rated capacity.
-
Detected during compressor running.
Model
L1
ARXN/ RXN25
9.5A
ARXN/ RXN35
10.0A
ARXN/ RXN50
12.0A
ARXN/ RXN60
12.0A
-
When the input current for running compressor exceeds L2, running frequency will be reduced by 1 step.
If current still exceeds L2, frequency will be reduced by another 1 step until total current falls between
L2 and L3.
-
This protection cut in when the input current exceeds L1 for 2 seconds – (ARXN/RXN LV1B (9))
Compressor will stop and it is considered total current overload.
-
If input current <L3, the compressor frequency is reset based on the OD ambient, set and room
temperature.
OIL RECOVERY CONTROL
-
When the compressor operates for certain duration at low frequency, the oil level in the compressor may
become low due to incomplete oil return.
-
To prevent damage to the compressor or compressor lock due to low oil lever.
-
To promote refrigerant flow to carry the oil back to the compressor.
Entering condition:
•
Compressor rotation < 35 Hz, at the end of a 20 minutes timer: set lower limit rotation to 35 Hz
& EXV opening is fixed at current o 50 pulse. This control is reset when rotation > 35
Hz.
Содержание SM-12-012
Страница 1: ...Service Manual SM Inverter_ i Air Conditioners Service Manual Split Inverter SM 12 012...
Страница 22: ...Service Manual SM Inverter_ i 22...
Страница 26: ...Service Manual SM Inverter_ i 26...
Страница 45: ...Service Manual SM Inverter_ i 45 Troubleshooting...
Страница 47: ...Service Manual SM Inverter_ i 47...
Страница 49: ...Service Manual SM Inverter_ i 49 ATXN FTXN 25 35 LV1B 9 ARXN RXN 25 35 LV1B 9 4 0 Wiring Connection...
Страница 50: ...Service Manual SM Inverter_ i 50 ATXN FTXN 50 60 LV1B 9 ARXN RXN50 60 LV1B 9...
Страница 51: ...Service Manual SM Inverter_ i 51 Refrigerant Diagram ATXN FTXN 25 35 50 60 LV1B 9...
Страница 52: ...Service Manual SM Inverter_ i 52 ARXN RXN 25 35 50 60 LV1B 9 Appendix Resistance value when 25 C...