Service Manual SM-Inverter_(i)
6
•
Heating operation: Tr < Ts
ID-OD COMMUNICATION
-
Master by outdoor unit.
-
Indoor controller board will transmit signal to outdoor controller board every 0.5s. Outdoor unit will
response to indoor once the valid data is received.
-
If the data communication line between indoor and outdoor disrupted for 15s continuously, compressor
will stop, OD fan stop with fan OFF timer. ID LED blinks error.
-
If the communication resumes within 15s, error code is clear and compressor restarts after 3 minutes.
-
If the communication does not resume after 15s, unit unable to restart and the error keep blinking.