Service Manual SM-Inverter_(i)
5
Heat Mode:
-
When Ts > Tr - 1.0°C
•
Comp, ID Fan and OD Fan ON.
-
When Tr
≥
Ts + 1.5°C
•
Compressor and Outdoor Fan OFF.
•
Indoor Fan off if indoor coil
≤
20°C.
Tr = Room Temperature
Ts = Set Temperature
When heating load is too small, and the room temperature still rising above compressor cut off point, compressor
will stop.
FAN MODE
-
Only High, Medium and Low fan speeds are allowed.
-
When changing cool mode to fan mode, the compressor will stop and OD fan stops based on fan OFF
control.
-
Compressor only ON if the minimum stop time is > 3 minutes and the user change back to cool mode.
-
Fan speed will maintain same as during fan mode.
AUTO MODE
-
For heat pump only
-
Mode switching point:
•
Heating
Cooling
Tr
≥
Ts + 2.5
•
Cooling
Heating
Tr
≤
Ts – 2.5
-
During initial operation
•
Cooling operation: Tr > Ts
Содержание SM-12-012
Страница 1: ...Service Manual SM Inverter_ i Air Conditioners Service Manual Split Inverter SM 12 012...
Страница 22: ...Service Manual SM Inverter_ i 22...
Страница 26: ...Service Manual SM Inverter_ i 26...
Страница 45: ...Service Manual SM Inverter_ i 45 Troubleshooting...
Страница 47: ...Service Manual SM Inverter_ i 47...
Страница 49: ...Service Manual SM Inverter_ i 49 ATXN FTXN 25 35 LV1B 9 ARXN RXN 25 35 LV1B 9 4 0 Wiring Connection...
Страница 50: ...Service Manual SM Inverter_ i 50 ATXN FTXN 50 60 LV1B 9 ARXN RXN50 60 LV1B 9...
Страница 51: ...Service Manual SM Inverter_ i 51 Refrigerant Diagram ATXN FTXN 25 35 50 60 LV1B 9...
Страница 52: ...Service Manual SM Inverter_ i 52 ARXN RXN 25 35 50 60 LV1B 9 Appendix Resistance value when 25 C...