Service Manual SM-Inverter_(i)
9
ATXN/FTXN-LV and ARXN/RXN-LV(1B/1B9):
DEFROST CONTROL
-
Condition for entering defrost
•
Compressor minimum run time – 6 minutes OR
•
Compressor accumulated run time of 45 minutes if Outdoor coil < 3
°
C.
-
Condition for terminating defrost
•
OD coil > 12
°
C or
•
Total defrost timer of 650 seconds.
OUTDOOR FAN CONTROL
-
Determine from
•
Compressor target rotation: higher fan speed with higher rotation.
•
Outdoor air temperature.
-
Cool mode: Higher fan speed with higher outdoor air temperature.
-
Heat mode: Higher fan speed with lower outdoor air temperature.
-
When compressor stops, fan OFF delay 30 seconds is carried out
INDOOR COIL FREEZE PREVENTION
-
Only available in cooling mode.
-
When the indoor coil temperature < 2°C, the compressor starts to drop the frequency.
-
This protection will cut in when:
•
Indoor coil temperature < 0°C for more than 180s. Compressor will stop, OD fan stop after 30s
and indoor fan can only run at lowest fan speed.
-
The unit can only be restarted after 3 minutes.
-
When the indoor coil temperature > 13°C, the compressor frequency will be reset based on the OD
ambient, room and set temperature.
Содержание SM-12-012
Страница 1: ...Service Manual SM Inverter_ i Air Conditioners Service Manual Split Inverter SM 12 012...
Страница 22: ...Service Manual SM Inverter_ i 22...
Страница 26: ...Service Manual SM Inverter_ i 26...
Страница 45: ...Service Manual SM Inverter_ i 45 Troubleshooting...
Страница 47: ...Service Manual SM Inverter_ i 47...
Страница 49: ...Service Manual SM Inverter_ i 49 ATXN FTXN 25 35 LV1B 9 ARXN RXN 25 35 LV1B 9 4 0 Wiring Connection...
Страница 50: ...Service Manual SM Inverter_ i 50 ATXN FTXN 50 60 LV1B 9 ARXN RXN50 60 LV1B 9...
Страница 51: ...Service Manual SM Inverter_ i 51 Refrigerant Diagram ATXN FTXN 25 35 50 60 LV1B 9...
Страница 52: ...Service Manual SM Inverter_ i 52 ARXN RXN 25 35 50 60 LV1B 9 Appendix Resistance value when 25 C...