Field Setting from Remote Controller
Field Setting
69
Graph 3
Target evaporating temperature control when "low humidity appli freeze up operation
prevention" is selected. Field setting 16(26)-2-04:
Note:
Change
thermostat
control
In order to increase continuous operation of the unit in low latent heat applications and avoid the
rise of temperature after thermostat OFF, the thermostat control will be changed when using
field settings 16(26)-2-03 & 16(26)-2-04.
Thermostat ON
∆
Trs
≥
0.5 °C (No change from standard setting)
Thermostat OFF
∆
Trs
≤
-2.0 °C for 5 minutes continuously.
∆
Trs
≤
4.5 °C
Te target
(˚C)
Te target acceptable area
Remote controller setting temp.
Te target limited
≤
20˚C
(to protect the comp.)
Te (see note) target acceptable area
Indoor temp.
>
setting
→
Te target down
Indoor temp.
<
setting
→
Te target up
Te target limited
≥
2˚C
(not to freeze)
Freeze protection
(40min. integrated coil temp.
≤
-1˚C)
Indoor Temp
(˚C DB)
Te by LP sensor
RZQG Series