Field Setting from Remote Controller
SiBE281013
62
Field Setting
2.4
Overview of the Field Setting on the Outdoor Units
Remote
controller
settings
The table below contains the remote controller settings.
Jumpers
The table below contains the jumper field settings.
Factory settings
The table below contains the factory settings of all outdoor units
Mode
No.
First
Code
No.
Description
Second Code No.
Details
01
02
03
04
05
16 (26)
0
Night time low
noise operation
Disabled
(Factory
setting)
Automatic
low noise
activation
Capacity
preceding
setting
(when
using
KRP58
option)
Automatic
low noise +
capacity
preceding
—
Refer to
P63.
1
Automatic low
noise start and
stop time
—
—
22h00 ~
06h00
22h00 ~
08h00
(Factory)
20h00 ~
08h00
Refer to
P63.
2
EDP room
setting
Disabled
(Factory
setting)
—
EDP room
setting
EDP room
s
no freeze
up
—
Refer to
P66.
3
Defrost starting
setting
Standard
(Factory
setting)
Defrost
slow
starting
setting
Defrost
quick
starting
setting
—
—
Refer to
P70.
Jumper
Label on PCB
(A1P)
Function
Details
JX5
JX5
Set as Cooling Only, For RZQG71·100LV1B
For RZQG125·140LV1B,
use the other PCB set as
Cooling Only (no JX5)
Mode No.
First Code No.
Second Code No.
26
0
01
1
04
2
01
3
01