SiBE281013
Troubleshooting by Remote Controller
Service Diagnosis
113
4.8
Transmission Error (between Indoor Unit PCB and
Adaptor PCB)
Remote
Controller
Display
C1
Applicable
Models
FCQG
Method of Error
Detection
Check the condition of transmission between indoor unit PCB (A1P) and adaptor PCB (A2P)
using micro-computer.
Error Decision
Conditions
When normal transmission is not conducted for certain duration (15 seconds or more). After 60
seconds, error is display on the remote controller.
Supposed
Causes
Connection defect of the connector indoor unit PCB (A1P) and adaptor PCB (A2P)
Defective indoor unit PCB (A1P)
Defective adaptor PCB (A2P)
External factor (Noise, etc.)