Wired Remote Controller
SiBE281013
16
Remote Controller
1.4
Centralized Control Group No. Setting
1.4.1 BRC1D528
In order to conduct the central remote control using the central remote controller and the unified
ON/OFF controller, Group No. settings should be made by group using the operating remote
controller.
Make Group No. settings for central remote control using the operating remote controller.
1. During normal mode, press and hold the “
” button for 4 seconds or more to enter the
"Field Setting Mode".
2. Select the Mode No. “
00
” with the “
” button.
3. Select the Group No. for each group with the “
” button.
(Group numbers increase in the order of 1-00, 1-01, ... 1-15, 2-00, ... 4-15.)
4. Press “
” or “
” button to set the selected Group No.
5. Press “
” button to return to the normal mode.
BRC1D528
NOTICE
Enter the group No. and installation place of the indoor unit into the installation table. Be sure to
keep the installation table with the operation manual for maintenance.
TEST
TEST
4
1,5
3
2
Group No.
Mode No.
Field setting
mode