Function Details
SiBE281013
30
Function and Control
z
In dry operation
Note:
∗
1: The thermistor to detect room temperature is as follows according to field setting.
· Factory setting: Indoor unit suction air thermistor
· When set to remote controller thermistor: Indoor air thermistor in the remote controller
3.1.3 Switchable Fan Speed
The setting airflow rate when the thermo. is turned on and off by operation mode is as shown
below. The airflow rate when the thermo. is turned off can be changed in field setting. The table
below shows the factory setting.
3.1.4 Swing Pattern Selection
Swing flaps operate as shown in the table below.
3.1.5 Drain Pump Control (Only for FCQG)
Cooling / Dry Operation
Normally drain pump ON (Thermostat ON/OFF)
Tro > 24ºC
16ºC
≥
Tro
24ºC
≥
Tro > 16ºC
∆
T < -2.5ºC
∆
> -1ºC
Thermostat OFF
Dry operation
∆
T < -2ºC
∆
> -1ºC
Thermostat OFF
Dry operation
Tr < 13ºC
Tr > 15ºC
Thermostat OFF
Dry operation
Fan
Cooling
Thermostat ON
Set
Thermostat OFF
Set
Program Dry
Thermostat ON
L
Thermostat OFF
OFF
Heating
Thermostat ON
Set
Thermostat OFF
LL
Fan
Set
Stop
OFF
Fan
Cooling
Flap Set
Thermostat ON
Set
Thermostat OFF
Set
Swing Set
Thermostat ON
Swing
Thermostat OFF
Swing
Program Dry
Flap Set
Thermostat ON
Set
Thermostat OFF
Set
Swing Set
Thermostat ON
Swing
Thermostat OFF
Swing
Heating
Flap Set
Thermostat ON
Set
Thermostat OFF
Horizontal
Swing Set
Thermostat ON
Swing
Thermostat OFF
Horizontal
Fan
Flap Set
Set
Stop
Swing Set
Swing