• Split Sky Air • Outdoor Units

6

• Outdoor Units • R-410A • RZQ-DV1

2

Specifications

2-1  NOMINAL CAPACITY AND NOMINAL INPUT

RZQ71D7V1B

RZQ100D7V1B

RZQ125D7V1B

RZQ140D7V1B

For combination 
indoor units + outdoor 
units

Indoor Units

FCQH71D7VEB

FCQH100D7VEB

FCQH125D7VEB

FCQH140D7VEB

Cooling capacity

Standard

kW

7.1

10.0

12.5

14.0

Heating capacity

Standard

kW

8.0

11.2

14.0

16.0

Power Input

Cooling

Standard

kW

1.88

2.50

3.48

4.36

Heating

Standard

kW

1.92

2.47

3.46

4.29

For combination 
indoor units + outdoor 
units

EER

Nominal

3.78

4.00

3.59

3.21

COP

Nominal

4.16

4.53

4.05

3.73

Energy Label

Cooling

A

Heating

A

Annual energy consumption

kWh

940

1,250

1,740

2,180

Indoor Units

FBQ71C7VEB

FBQ100C7VEB

FBQ125C7VEB

FBQ140C7VEB

Cooling capacity

Standard

kW

7.1

10.0

12.5

13.4

Heating capacity

Standard

kW

8.0

11.2

14.0

15.0

Power Input

Cooling

Standard

kW

2.09

2.70

3.59

4.45

Heating

Standard

kW

2.08

2.69

3.87

4.40

For combination 
indoor units + outdoor 
units

EER

Nominal

3.39

3.70

3.48

3.01

COP

Nominal

3.85

4.16

3.62

3.41

Energy  Label

Cooling

A

A

A

B

Heating

A

A

A

B

Annual energy consumption

kWh

1,047

1,351

1,796

2,226

Indoor Units

FCQ71C7VEB

FCQ100C7VEB

FCQ125C7VEB

FCQ140C7VEB

Cooling capacity

Standard

kW

7.1

10.0

12.5

14.0

Heating capacity

Standard

kW

8.0

11.2

14.0

16.0

Power Input

Cooling

Standard

kW

2.11

2.64

3.70

5.11

Heating

Standard

kW

2.21

2.96

3.88

4.89

For combination 
indoor units + outdoor 
units

EER

Nominal

3.36

3.79

3.38

2.74

COP

Nominal

3.62

3.78

3.61

3.27

Energy Label

Cooling

A

A

A

D

Heating

A

A

A

C

Annual energy consumption

kWh

1,055

1,319

1,849

2,555

Indoor Units

FHQ71BVV1B

FHQ100BVV1B

FHQ125BVV1B

Cooling capacity

Standard

kW

7.1

10.0

12.5

Heating capacity

Standard

kW

8.0

11.2

14.0

Power Input

Cooling

Standard

kW

2.34

3.14

4.24

Heating

Standard

kW

2.58

3.43

4.28

For combination 
indoor units + outdoor 
units

EER

Nominal

3.03

3.18

2.95

COP

Nominal

3.10

3.27

3.27

Energy Label

Cooling

B

B

C

Heating

D

C

C

Annual energy consumption

kWh

1,172

1,572

2,119

Indoor Units

FAQ71BVV1B

FAQ100BVV1B

FDQ125B8V3B9

Cooling capacity

Standard

kW

7.1

10.0

12.5

Heating capacity

Standard

kW

8.0

11.2

14.0

Power Input

Cooling

Standard

kW

2.28

3.29

3.96

Heating

Standard

kW

2.33

3.21

3.61

For combination 
indoor units + outdoor 
units

EER

Nominal

3.11

3.04

3.16

COP

Nominal

3.43

3.49

3.88

Energy Label

Cooling

B

B

B

Heating

B

B

A

Annual energy consumption

kWh

1,141

1,645

1,978

Indoor Units

FUQ71BVV1B

FUQ100BVV1B

FUQ125BVV1B

Cooling capacity

Standard

kW

7.1

10.0

12.5

Heating capacity

Standard

kW

8.0

11.2

14.0

Power Input

Cooling

Standard

kW

2.21

2.97

3.96

Heating

Standard

kW

2.34

3.31

4.26

Содержание RZQ-DV1

Страница 1: ...technical data Split Sky Air air conditioning systems RZQ DV1 EEDEN09 100...

Страница 2: ...rovent Directory Daikin s unique position as a man ufacturer of air conditioning equip ment compressors and refrige rants has led to its close involve ment in environmental issues For several years Da...

Страница 3: ...technical data Split Sky Air air conditioning systems RZQ DV1 EEDEN09 100...

Страница 4: ...8 3 Electrical data 9 4 Options 10 5 Capacity tables 11 Combination table 11 Cooling capacity tables 13 Heating capacity tables 19 6 Dimensional drawing centre of gravity 24 Dimensional drawing 24 Ce...

Страница 5: ...ency and very low sound level An inverter driven compressor allows the capacity to be adjusted precisely to match variations in room and outside temperatures During start up the room can be cooled dow...

Страница 6: ...rd kW 7 1 10 0 12 5 14 0 Heating capacity Standard kW 8 0 11 2 14 0 16 0 Power Input Cooling Standard kW 2 11 2 64 3 70 5 11 Heating Standard kW 2 21 2 96 3 88 4 89 For combination indoorunits outdoor...

Страница 7: ...nti corrosion treatment PE Fan Type Propeller Discharge direction Horizontal Quantity 1 2 2 2 Air Flow Rate nominal at 230V Cooling m min 52 96 100 97 Heating m min 48 90 90 90 Motor Quantity 1 2 2 2...

Страница 8: ...ies Item Tie wraps Quantity 2 2 2 2 Item Installation manual Quantity 1 1 1 1 Notes Nominal cooling capacities are based on indoor temperature 27 CDB 19 CWB outdoor temperature 35 CDB equivalent refri...

Страница 9: ...wing conditions Power supply 50Hz 230V Cooling Indoor temperature 27 CDB 19 CWB Outdoor temperature 35 CDB Heating Indoor temperature 20 0 CDB Outdoor temperature 7 0 CDB 6 0 CWB 2 TOCA means the tota...

Страница 10: ...7V1B RZQS125D7V1B RZQS140D7V1B RZQ100B8W1B RZQ125B8W1B RZQ140B8W1B Central drain plug EKDK04 Refrigerant branch piping Twin KHRQ22M20TA KHRQ58T see note Triple KHRQ127H KHRQ58H see note Double twin KH...

Страница 11: ...mounted High ESP duct Floor standing Multi Combination Possibilities P Pair 2 Twin 3 Triple 4 Double twin NOTES 1 Individual indoor capacities are not given because the combinations are for simultaneo...

Страница 12: ...apacities are not given because the combinations are for simultaneous operation indoor units installed in same room 2 When different indoor models are used in combination designate the infrared remote...

Страница 13: ...t at standard condition 3 SHC is based on each EWB and EDB SHC SHC correction for other dry bulb SHC 0 02 x AFR m 3 min x 1 BF x DB EDB Add SHC to SHC 4 Capacities are based on following conditions Ou...

Страница 14: ...ulb SHC 0 02 x AFR m 3 min x 1 BF x DB EDB Add SHC to SHC 4 Capacities are based on following conditions Outdoor air 85 RH however the condition on nominal capacity is 7 CDB 6 CWB heating Correspondin...

Страница 15: ...conditions Outdoor air 85 RH however the condition on nominal capacity is 7 CDB 6 CWB heating Corresponding refrigerant piping length 5 0 m Level difference 0 m 5 Coefficient of power input is the per...

Страница 16: ...based on following conditions Outdoor air 85 RH however the condition on nominal capacity is 7 CDB 6 CWB heating Corresponding refrigerant piping length 5 0 m Level difference 0 m 5 Coefficient of po...

Страница 17: ...at standard conditions On the figure the mark Q show rated capacity and rated coefficient of power input However the max capacity is not guaranteed except at standard condition 3 SHC is based on each...

Страница 18: ...tdoor Units 18 Outdoor Units R 410A RZQ DV1 5 Capacity tables 5 2 Cooling capacity tables 3TW26062 1 RZQ71 140DV1 Capacity Field piping length m Cooling Heating Capacity in function of field piping le...

Страница 19: ...coefficient of power input 4 SHC is based on each EWB and EDB SHC SHC correction for other dry bulb SHC 0 02 x AFR m 3 min x 1 BF x DB EDB Add SHC to SHC 5 Capacities are based on following conditions...

Страница 20: ...y bulb SHC 0 02 x AFR m 3 min x 1 BF x DB EDB Add SHC to SHC 5 Capacities are based on following conditions Outdoor air 85 RH however the condition on nominal capacity is 7 CDB 6 CWB heating Correspon...

Страница 21: ...ng conditions Outdoor air 85 RH however the condition on nominal capacity is 7 CDB 6 CWB heating Corresponding refrigerant piping length 5 0 m Level difference 0 m 6 Coefficient of power input is the...

Страница 22: ...are based on following conditions Outdoor air 85 RH however the condition on nominal capacity is 7 CDB 6 CWB heating Corresponding refrigerant piping length 5 0 m Level difference 0 m 6 Coefficient of...

Страница 23: ...rated coefficient of power input However the max capacity is not guaranteed except at standard condition 3 On the tables Q show rated capacity and rated coefficient of power input 4 SHC is based on ea...

Страница 24: ...igerant piping intake 6 Power supply wiring intake knock out hole J34 7 Control wiring intake Knock out hole J27 8 Drain outlet RZQ71DV1 Hole for anchor bolt 4 M12 3TW26071 1 unit mm 1 Gas pipe connec...

Страница 25: ...Outdoor Units R 410A RZQ DV1 1 6 Split Sky Air Outdoor Units 25 6 Dimensional drawing centre of gravity 6 2 Centre of gravity 4TW30469 3 RZQ71DV1 4TW31729 4 RZQ100 140DV1...

Страница 26: ...ure switch Filter Low pressure sensor 3TW29165 2 RZQ71 140DV1 Twin Indoor unit Field piping J15 9 Field piping J9 5 Low pressure sensor Heat exchanger Filter Stop valve with service port 5 16 flare Fi...

Страница 27: ...branch and the indoor units should have the same size as the indoor connections 3TW29165 4 RZQ125 140DV1 Double twin Indoor unit Field piping J15 9 Field piping J9 5 Low pressure sensor Heat exchanger...

Страница 28: ...f compressor terminal Back Outdoor Note4 2TW29166 2 A1P Printed circuit board Main A2P Printed circuit board Inverter A3P Printed circuit board Noise filter A4P Printed circuit board BS1 BS4 Push butt...

Страница 29: ...ns 3 dB A A weighted sound pressure level A scale according to IEC 4 Reference acoustic pressure 0dB 20 Pa Measuring location discharge side M High tap 3TW31687 2 Sound pressure level dB Octave band c...

Страница 30: ...ons 3 dB A A weighted sound pressure level A scale according to IEC 4 Reference acoustic pressure 0dB 20 Pa Measuring location discharge side M High tap 3TW316707 2 Sound pressure level dB Octave band...

Страница 31: ...B A A weighted sound pressure level A scale according to IEC 2 Reference acoustic intensity 0dB 10E 6 W m2 3 Measured according to ISO 3744 M High tap 3TW31697 1 Sound power level dB Octave band cente...

Страница 32: ...ow RZQ71 140DV1 A Non stacked installation 2 Obstacles exist in front of the air inlet B Stacked installation Legend C Multiple row installation Relation of dimensions of H A and L are shown in the ta...

Страница 33: ...ration pull down Allowable range of operation warming up Operation range Outdoor temp CWB Heating Indoor temp CWB Indoor temp CDB Cooling RZQ71 140DV1 EDP ROOM 3TW29163 2A NOTE 1 Depending on operatio...