• Outdoor Units • R-410A • RZQ-DV1
1
5
• Split Sky Air • Outdoor Units
15
5
Capacity tables
5 - 2
Cooling capacity tables
RZQ125DV1
Cooling
Cooling capacity
Indoor
Outdoor temp. (°CDB)
EWB
EDB
25
30
35
40
(°C)
(°C)
TC
(kW)
SHC
(kW)
CPI
(-)
TC
(kW)
SHC
(kW)
CPI
(-)
TC
(kW)
SHC
(kW)
CPI
(-)
TC
(kW)
SHC
(kW)
CPI
(-)
3D063307
SYMBOLS
AFR:
Air flow rate
(m
3
/min)
BF:
Bypass factor
EWB:
Entering wet bulb temp.
(°CWB)
EDB:
Entering dry bulb temp.
(°CDB)
TC:
Total cooling capacity
(kW)
SHC:
Sensible heating capacity
(kW)
PI:
Power input
(kW)
(comp.+outdoor fan motor)
CPI:
Coefficient of power input.
(-)
Caution:
TC and SHC are shown by kW
NOTES
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat
2. On the figure the mark
j
show the max. at standard conditions.
On the figure the mark
Q
show rated capacity and rated coefficient of power input.
However the max. capacity is not guaranteed, except at standard condition.
3. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.02 x AFR (m
3
/min.) x (1
−
BF) x (DB*
−
EDB)
Add SHC* to SHC.
4. Capacities are based on following conditions:
Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating)
Corresponding refrigerant piping length
: 5.0 m
Level difference
: 0 m
5. Coefficient of power input is the percentage when the rated valve is defined as 1.00.
6. The value contains less than 5% error acording to indoor unit type.
7. Air flow rate and BF are tabulated below.
(Pair)
Model
FCQH125D
FCQ125C
FBQ125C
FHQ125
FAQ125
FUQ125
AFR
(BF)
34
(0.19)
27.5
(0.19)
39
(0.16)
30
(0.13)
32
(0.13)
45
(0.25)
(Twin)
Model
FCQ60Cx2
FFQ60x2
FBQ60Cx2
FHQ60x2
AFR
(BF)
13.5x2
(0.21x2)
15x2
(0.11x2)
18x2
(0.15x2)
17x2
(0.2x2)
(Triple)
Model
FCQ50Cx3
FFQ50x3
FBQ50Cx3
FHQ50x3
AFR
(BF)
12.5x3
(0.21x3)
12x3
(0.16x3)
16x3
(0.16x3)
13x3
(0.1x3)
8. Rated power input of each model is tabulated below.
(Pair)
Model
FCQH125D
FCQ125C
FBQ125C
FHQ125
FAQ125
FUQ125
Cooling
3.48
3.70
3.59
4.24
3.96
3.96
(Twin)
Model
FCQ60Cx2
FFQ60x2
FBQ60x2
FHQ60x2
Cooling
3.89
3.93
3.80
4.24
(Triple)
Model
FCQ50Cx3
FFQ50x3
FBQ50x3
FHQ50x3
Cooling
3.89
3.93
3.80
4.24
Capacity range
Rated point
Cooling capacity (kW)
Coefficient
of
power
input.
(-)
(Double Twin)
Model
FCQ35Cx4
FFQ35x4
FBQ35Cx4
FHQ35x4
AFR
(BF)
10.5x4
(0.28x4)
10x4
(0.25x4)
16x4
(0.15x4)
13x4
(0.2x4)
(Double Twin)
Model
FCQ35Cx4
FFQ35x4
FBQ35x4
FHQ35x4
Cooling
3.89
3.93
3.80
4.24