• Outdoor Units • R-410A • RZQ-DV1

1

5

• Split Sky Air • Outdoor Units

21

5

Capacity tables

5 - 3

Heating capacity tables

RZQ125DV1

Heating

Heating capacity

Indoor

Outdoor temp. (°CDB)

EDB

-15

-10

-5

0

6

10

(°C)

TC

(kW)

CPI

(-)

TC

(kW)

CPI

(-)

TC

(kW)

CPI

(-)

TC

(kW)

CPI

(-)

TC

(kW)

CPI

(-)

TC
(-)

CPI

(-)

3D063307

SYMBOLS

AFR:

Air flow rate

(m

3

/min)

BF:

Bypass factor

EWB:

Entering wet bulb temp.

(°CWB)

EDB:

Entering dry bulb temp.

(°CDB)

TC:

Total heating capacity

(kW)

SHC:

Sensible heating capacity

(kW)

PI:

Power input

(kW)

(comp.+outdoor fan motor)

CPI:

Coefficient of power input.

(-)

Caution:
TC and SHC are shown by kW

NOTES

1. Ratings shown are net capacities which include a deduction for indoor fan motor heat
2. On the figure the mark

j

show the max. at standard conditions.

On the figure the mark

Q

show rated capacity and rated coefficient of power input.

However the max. capacity is not guaranteed, except at standard condition.

3. On the tables

Q

show rated capacity and rated coefficient of power input.

4. SHC is based on each EWB and EDB

SHC* = SHC correction for other dry bulb
SHC* = 0.02 x AFR (m

3

/min.) x (1

BF) x (DB*

EDB)

Add SHC* to SHC.

5. Capacities are based on following conditions:

Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating)
Corresponding refrigerant piping length

: 5.0 m

Level difference

: 0 m

6. Coefficient of power input is the percentage when the rated valve is defined as 1.00.
7. The value contains less than 5% error acording to indoor unit type.
8. Heating capacity include the drop of frost formation.
9. Air flow rate and BF are tabulated below.

(Pair)

Model

FCQH125D

FCQ125C

FBQ125C

FHQ125

FAQ125

FUQ125

AFR

(BF)

34

(0.19)

27.5

(0.19)

39

(0.16)

30

(0.13)

32

(0.13)

45

(0.25)

(Twin)

Model

FCQ60Cx2

FFQ60x2

FBQ60Cx2

FHQ60x2

AFR

(BF)

13.5x2

(0.21x2)

15x2

(0.11x2)

18x2

(0.15x2)

17x2

(0.2x2)

(Triple)

Model

FCQ50Cx3

FFQ50x3

FBQ50Cx3

FHQ50x3

AFR

(BF)

12.5x3

(0.21x3)

12x3

(0.16x3)

16x3

(0.16x3)

13x3

(0.1x3)

10. Rated power input of each model is tabulated below.

(Pair)

Model

FCQH125D

FCQ125C

FBQ125C

FHQ125

FAQ125

FUQ125

Heating

3.46

3.88

3.87

4.28

4.25

3.61

(Twin)

Model

FCQ60Cx2

FFQ60x2

FBQ60x2

FHQ60x2

Heating

4.07

4.17

4.08

4.50

(Triple)

Model

FCQ50Cx3

FFQ50x3

FBQ50x3

FHQ50x3

Heating

4.07

4.17

4.08

4.50

Capacity range

Rated point

Heating capacity (kW)

Coefficient

of

power

input.

(-)

(Double Twin)

Model

FCQ35Cx4

FFQ35x4

FBQ35Cx4

FHQ35x4

AFR

(BF)

10.5x4

(0.28x4)

10x4

(0.25x4)

16x4

(0.15x4)

13x4

(0.2x4)

(Double Twin)

Model

FCQ35Cx4

FFQ35x4

FBQ35x4

FHQ35x4

Heating

4.07

4.17

4.08

4.50

Содержание RZQ-DV1

Страница 1: ...technical data Split Sky Air air conditioning systems RZQ DV1 EEDEN09 100...

Страница 2: ...rovent Directory Daikin s unique position as a man ufacturer of air conditioning equip ment compressors and refrige rants has led to its close involve ment in environmental issues For several years Da...

Страница 3: ...technical data Split Sky Air air conditioning systems RZQ DV1 EEDEN09 100...

Страница 4: ...8 3 Electrical data 9 4 Options 10 5 Capacity tables 11 Combination table 11 Cooling capacity tables 13 Heating capacity tables 19 6 Dimensional drawing centre of gravity 24 Dimensional drawing 24 Ce...

Страница 5: ...ency and very low sound level An inverter driven compressor allows the capacity to be adjusted precisely to match variations in room and outside temperatures During start up the room can be cooled dow...

Страница 6: ...rd kW 7 1 10 0 12 5 14 0 Heating capacity Standard kW 8 0 11 2 14 0 16 0 Power Input Cooling Standard kW 2 11 2 64 3 70 5 11 Heating Standard kW 2 21 2 96 3 88 4 89 For combination indoorunits outdoor...

Страница 7: ...nti corrosion treatment PE Fan Type Propeller Discharge direction Horizontal Quantity 1 2 2 2 Air Flow Rate nominal at 230V Cooling m min 52 96 100 97 Heating m min 48 90 90 90 Motor Quantity 1 2 2 2...

Страница 8: ...ies Item Tie wraps Quantity 2 2 2 2 Item Installation manual Quantity 1 1 1 1 Notes Nominal cooling capacities are based on indoor temperature 27 CDB 19 CWB outdoor temperature 35 CDB equivalent refri...

Страница 9: ...wing conditions Power supply 50Hz 230V Cooling Indoor temperature 27 CDB 19 CWB Outdoor temperature 35 CDB Heating Indoor temperature 20 0 CDB Outdoor temperature 7 0 CDB 6 0 CWB 2 TOCA means the tota...

Страница 10: ...7V1B RZQS125D7V1B RZQS140D7V1B RZQ100B8W1B RZQ125B8W1B RZQ140B8W1B Central drain plug EKDK04 Refrigerant branch piping Twin KHRQ22M20TA KHRQ58T see note Triple KHRQ127H KHRQ58H see note Double twin KH...

Страница 11: ...mounted High ESP duct Floor standing Multi Combination Possibilities P Pair 2 Twin 3 Triple 4 Double twin NOTES 1 Individual indoor capacities are not given because the combinations are for simultaneo...

Страница 12: ...apacities are not given because the combinations are for simultaneous operation indoor units installed in same room 2 When different indoor models are used in combination designate the infrared remote...

Страница 13: ...t at standard condition 3 SHC is based on each EWB and EDB SHC SHC correction for other dry bulb SHC 0 02 x AFR m 3 min x 1 BF x DB EDB Add SHC to SHC 4 Capacities are based on following conditions Ou...

Страница 14: ...ulb SHC 0 02 x AFR m 3 min x 1 BF x DB EDB Add SHC to SHC 4 Capacities are based on following conditions Outdoor air 85 RH however the condition on nominal capacity is 7 CDB 6 CWB heating Correspondin...

Страница 15: ...conditions Outdoor air 85 RH however the condition on nominal capacity is 7 CDB 6 CWB heating Corresponding refrigerant piping length 5 0 m Level difference 0 m 5 Coefficient of power input is the per...

Страница 16: ...based on following conditions Outdoor air 85 RH however the condition on nominal capacity is 7 CDB 6 CWB heating Corresponding refrigerant piping length 5 0 m Level difference 0 m 5 Coefficient of po...

Страница 17: ...at standard conditions On the figure the mark Q show rated capacity and rated coefficient of power input However the max capacity is not guaranteed except at standard condition 3 SHC is based on each...

Страница 18: ...tdoor Units 18 Outdoor Units R 410A RZQ DV1 5 Capacity tables 5 2 Cooling capacity tables 3TW26062 1 RZQ71 140DV1 Capacity Field piping length m Cooling Heating Capacity in function of field piping le...

Страница 19: ...coefficient of power input 4 SHC is based on each EWB and EDB SHC SHC correction for other dry bulb SHC 0 02 x AFR m 3 min x 1 BF x DB EDB Add SHC to SHC 5 Capacities are based on following conditions...

Страница 20: ...y bulb SHC 0 02 x AFR m 3 min x 1 BF x DB EDB Add SHC to SHC 5 Capacities are based on following conditions Outdoor air 85 RH however the condition on nominal capacity is 7 CDB 6 CWB heating Correspon...

Страница 21: ...ng conditions Outdoor air 85 RH however the condition on nominal capacity is 7 CDB 6 CWB heating Corresponding refrigerant piping length 5 0 m Level difference 0 m 6 Coefficient of power input is the...

Страница 22: ...are based on following conditions Outdoor air 85 RH however the condition on nominal capacity is 7 CDB 6 CWB heating Corresponding refrigerant piping length 5 0 m Level difference 0 m 6 Coefficient of...

Страница 23: ...rated coefficient of power input However the max capacity is not guaranteed except at standard condition 3 On the tables Q show rated capacity and rated coefficient of power input 4 SHC is based on ea...

Страница 24: ...igerant piping intake 6 Power supply wiring intake knock out hole J34 7 Control wiring intake Knock out hole J27 8 Drain outlet RZQ71DV1 Hole for anchor bolt 4 M12 3TW26071 1 unit mm 1 Gas pipe connec...

Страница 25: ...Outdoor Units R 410A RZQ DV1 1 6 Split Sky Air Outdoor Units 25 6 Dimensional drawing centre of gravity 6 2 Centre of gravity 4TW30469 3 RZQ71DV1 4TW31729 4 RZQ100 140DV1...

Страница 26: ...ure switch Filter Low pressure sensor 3TW29165 2 RZQ71 140DV1 Twin Indoor unit Field piping J15 9 Field piping J9 5 Low pressure sensor Heat exchanger Filter Stop valve with service port 5 16 flare Fi...

Страница 27: ...branch and the indoor units should have the same size as the indoor connections 3TW29165 4 RZQ125 140DV1 Double twin Indoor unit Field piping J15 9 Field piping J9 5 Low pressure sensor Heat exchanger...

Страница 28: ...f compressor terminal Back Outdoor Note4 2TW29166 2 A1P Printed circuit board Main A2P Printed circuit board Inverter A3P Printed circuit board Noise filter A4P Printed circuit board BS1 BS4 Push butt...

Страница 29: ...ns 3 dB A A weighted sound pressure level A scale according to IEC 4 Reference acoustic pressure 0dB 20 Pa Measuring location discharge side M High tap 3TW31687 2 Sound pressure level dB Octave band c...

Страница 30: ...ons 3 dB A A weighted sound pressure level A scale according to IEC 4 Reference acoustic pressure 0dB 20 Pa Measuring location discharge side M High tap 3TW316707 2 Sound pressure level dB Octave band...

Страница 31: ...B A A weighted sound pressure level A scale according to IEC 2 Reference acoustic intensity 0dB 10E 6 W m2 3 Measured according to ISO 3744 M High tap 3TW31697 1 Sound power level dB Octave band cente...

Страница 32: ...ow RZQ71 140DV1 A Non stacked installation 2 Obstacles exist in front of the air inlet B Stacked installation Legend C Multiple row installation Relation of dimensions of H A and L are shown in the ta...

Страница 33: ...ration pull down Allowable range of operation warming up Operation range Outdoor temp CWB Heating Indoor temp CWB Indoor temp CDB Cooling RZQ71 140DV1 EDP ROOM 3TW29163 2A NOTE 1 Depending on operatio...

Отзывы: