• Split Sky Air • Outdoor Units
8
• Outdoor Units • R-410A • RZQ-DV1
2
Specifications
Refrigerant
Type
R-410A
Charge
kg
2.75
3.95
3.95
3.95
Control
Expansion valve (electronic type)
Nr of Circuits
1
1
1
1
Refrigerant Oil
Type
FVC50K
Daphne FVC68D
Charged Volume
l
0.75
1.0
1.0
1.0
Piping connections
Liquid (OD)
Quantity
1
1
1
1
Type
Flare connection
Diameter (OD) mm
9.52
9.52
9.52
9.52
Gas
Quantity
1
1
1
1
Type
Flare connection
Diameter (OD) mm
15.9
15.9
15.9
15.9
Drain
Quantity
3
3
3
3
Type
Hole
Diameter (OD) mm
26
26
26
26
Piping Length
Minimum
m
5
5
5
5
Maximum
m
50
75
75
75
Equivalent
m
70
95
95
95
Chargeless
m
30
30
30
30
Additional Refrigerant Charge
kg/m
See installation manual 4PW48323-1
Installation height
difference
Maximum
m
30.0
30.0
30.0
30.0
Max. internunit level difference
m
0.5
0.5
0.5
0.5
Heat Insulation
Both liquid and gas pipes
Defrost Method
Pressure equalising
Defrost Control
Temperature
Capacity Control Method
Inverter controlled
Safety Devices
High pressure switch
Fan motor thermal protector
Fuse
Standard
Accessories
Item
Tie-wraps
Quantity
2
2
2
2
Item
Installation manual
Quantity
1
1
1
1
Notes
Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor
temperature : 35°CDB, equivalent refrigerant piping : 5m, level difference : 0m.
Nominal heating capacities are based on: indoor temperature: 20°CDB; outdoor temperature:
7°CDB, 6°CWB; equivalent refrigerant piping length: 5m; level difference: 0m
2-3 ELECTRICAL SPECIFICATIONS
RZQ71D7V1B
RZQ100D7V1B
RZQ125D7V1B
RZQ140D7V1B
Power Supply
Name
V1
Phase
1~
Frequency
Hz
50
50
50
50
Voltage
V
220-240
Voltage range
Minimum V
198
198
198
198
Maximum V
264
264
264
264
Current
Recomended fuses
A
20
32
32
32
Wiring
connections
For Power
Supply
Remark
See installation manual 4PW48323-1
For connection
with indoor
Remark
See installation manual 4PW48323-1
Power Supply Intake
Outdoor unit only
Notes
See separate drawings for electrical data
(1) European/international technical standard setting the limits for harmonic currents produced by equipment
connected to public low-voltage system with input current > 16A smaller than or equal to 75A per phase.
(2) Short-circuit power
Power supply to the FDQ
indoor unit is separate
2-2 TECHNICAL SPECIFICATIONS
RZQ71D7V1B
RZQ100D7V1B
RZQ125D7V1B
RZQ140D7V1B