Field Settings for FDMQ, FFQ Series
SiUS092230EA
222
Part 7 Trial Operation and Field Settings
Note(s)
Multiple Settings
A or b
When the indoor unit is controlled by an outside controller (central remote controller, etc.), the
indoor unit sometimes does not respond to ON/OFF command or temperature setting command
from the wireless remote controller. Check what setting the customer needs and make the multiple
setting as shown below.
After Setting
Stick the Unit No. label on the receiver and the back of the wireless remote controller.
Set the Unit No. of the receiver and the wireless remote controller to be the equal. If the settings
differ, the signal from the remote controller cannot be transmitted.
Remote Controller
Indoor Unit
Multiple settings
Remote controller
display
To control other air
conditions and units
For other than on left
A
: Standard
All items displayed.
Commands other than
ON/OFF and
temperature setting
accepted.
(1 LONG BEEP or 3
SHORT BEEPS
emitted)
All commands
accepted.
(2 SHORT BEEPS)
b
: Multi System
Operations remain
displayed shortly after
execution
All commands accepted. (2 SHORT BEEPS)
1
Unit No. label (5)
Wireless remote
controller (2)
(R25081)
Содержание RX-W Series
Страница 1: ... Applied Models Inverter Pair Heat Pump Service Manual SiUS092230EA Inverter Pair RX W Series ...
Страница 15: ...SiUS092230EA Part 1 General Information 9 1 Applicable Models 10 2 Functions 11 Part 1 General Information ...
Страница 107: ...SiUS092230EA BRC082A41W BRC082A42W S Part 5 Remote Controller 101 4 BRC082A41W BRC082A42W S R23936 R23937 ...
Страница 151: ...SiUS092230EA Troubleshooting for FDMQ FFQ Series Part 6 Service Diagnosis 145 Reference Check No 02 Refer to P 191 ...
Страница 207: ...SiUS092230EA Check Part 6 Service Diagnosis 201 15 18 24 class R25105 1 2 3 4 Multimeter ...
Страница 209: ...SiUS092230EA Check Part 6 Service Diagnosis 203 15 18 24 class R20704 W V U DC_P1 DC_N1 ...
Страница 238: ...Piping Diagrams SiUS092230EA 232 Part 8 Appendix 1 2 Outdoor Unit RX09 12WMVJU9 RX15 18WMVJU9 3D135014 3D141501 ...
Страница 239: ...SiUS092230EA Piping Diagrams Part 8 Appendix 233 RX24WMVJU9 3D141502 ...
Страница 246: ...Operation Limit SiUS092230EA 240 Part 8 Appendix 3 Operation Limit RX09 12 15 18 24WMVJU9 3D092209F ...