Troubleshooting for Outdoor Unit
SiUS092230EA
158
Part 6 Service Diagnosis
7. Troubleshooting for Outdoor Unit
7.1 Outdoor Unit PCB Abnormality
Error Code
E1
Method of Error
Detection
The system checks if the microprocessor is working in order.
The system checks if the zero-cross signal comes in properly.
Error Decision
Conditions
The microprocessor program runs out of control.
The zero-cross signal is not detected.
Supposed
Causes
Defective outdoor unit PCB
Noise
Momentary drop of voltage
Momentary power failure
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Continuously ON, OFF
Blink
YES
(R24717)
NO
Replace the outdoor unit
PCB (main PCB).
Ground the system.
Zero-cross signal
abnormality.
Replace the outdoor unit
PCB (main PCB).
Check if the outdoor unit is
grounded.
Is LED A blinking?
Grounded?
Turn on the power again.
Содержание RX-W Series
Страница 1: ... Applied Models Inverter Pair Heat Pump Service Manual SiUS092230EA Inverter Pair RX W Series ...
Страница 15: ...SiUS092230EA Part 1 General Information 9 1 Applicable Models 10 2 Functions 11 Part 1 General Information ...
Страница 107: ...SiUS092230EA BRC082A41W BRC082A42W S Part 5 Remote Controller 101 4 BRC082A41W BRC082A42W S R23936 R23937 ...
Страница 151: ...SiUS092230EA Troubleshooting for FDMQ FFQ Series Part 6 Service Diagnosis 145 Reference Check No 02 Refer to P 191 ...
Страница 207: ...SiUS092230EA Check Part 6 Service Diagnosis 201 15 18 24 class R25105 1 2 3 4 Multimeter ...
Страница 209: ...SiUS092230EA Check Part 6 Service Diagnosis 203 15 18 24 class R20704 W V U DC_P1 DC_N1 ...
Страница 238: ...Piping Diagrams SiUS092230EA 232 Part 8 Appendix 1 2 Outdoor Unit RX09 12WMVJU9 RX15 18WMVJU9 3D135014 3D141501 ...
Страница 239: ...SiUS092230EA Piping Diagrams Part 8 Appendix 233 RX24WMVJU9 3D141502 ...
Страница 246: ...Operation Limit SiUS092230EA 240 Part 8 Appendix 3 Operation Limit RX09 12 15 18 24WMVJU9 3D092209F ...