Control Specification
SiUS092230EA
88
Part 4 Functions and Control
FFQ
The operating frequency limitation is judged with the indoor heat exchanger temperature.
R4003916
5.8 Heating
Peak-cut
Control
During heating operation, the indoor heat exchanger temperature determines the frequency upper
limit to prevent abnormal high pressure.
The operating frequency limitation is judged with the indoor heat exchanger temperature.
Reset zone
Up zone
Keep zone
Dropping zone
Stop zone
13°C (55.4°F)
7°C (44.6°F)
3°C (37.4°F)
0°C (32.0°F)
5°C (41.0°F)
Indoor heat exchanger
temperature (R2T)
Zone
Control
Stop zone
When the temperature reaches the stop zone, the compressor stops.
Dropping zone
The upper limit of frequency decreases.
Keep zone
The upper limit of frequency is kept.
Up zone
The upper limit of frequency increases.
Reset zone
The upper limit of frequency is canceled.
09/12 class
15 class
18 class
24 class
(°C)
(°F)
(°C)
(°F)
(°C)
(°F)
(°C)
(°F)
A
57.5
135.5
60
140.0
60
140.0
60
140.0
B
55
131.0
54
129.2
55
131.0
54
129.2
C
52
125.6
51
123.8
52
125.6
51
123.8
D
50
122.0
49
120.2
50
122.0
49
120.2
E
45
113.0
44
111.2
45
113.0
44
111.2
Indoor heat exchanger
temperature
Stop zone
Dropping zone
Keep zone
Up zone
Reset zone
(R23928)
D
C
B
A
E
Содержание RX-W Series
Страница 1: ... Applied Models Inverter Pair Heat Pump Service Manual SiUS092230EA Inverter Pair RX W Series ...
Страница 15: ...SiUS092230EA Part 1 General Information 9 1 Applicable Models 10 2 Functions 11 Part 1 General Information ...
Страница 107: ...SiUS092230EA BRC082A41W BRC082A42W S Part 5 Remote Controller 101 4 BRC082A41W BRC082A42W S R23936 R23937 ...
Страница 151: ...SiUS092230EA Troubleshooting for FDMQ FFQ Series Part 6 Service Diagnosis 145 Reference Check No 02 Refer to P 191 ...
Страница 207: ...SiUS092230EA Check Part 6 Service Diagnosis 201 15 18 24 class R25105 1 2 3 4 Multimeter ...
Страница 209: ...SiUS092230EA Check Part 6 Service Diagnosis 203 15 18 24 class R20704 W V U DC_P1 DC_N1 ...
Страница 238: ...Piping Diagrams SiUS092230EA 232 Part 8 Appendix 1 2 Outdoor Unit RX09 12WMVJU9 RX15 18WMVJU9 3D135014 3D141501 ...
Страница 239: ...SiUS092230EA Piping Diagrams Part 8 Appendix 233 RX24WMVJU9 3D141502 ...
Страница 246: ...Operation Limit SiUS092230EA 240 Part 8 Appendix 3 Operation Limit RX09 12 15 18 24WMVJU9 3D092209F ...