SiUS092230EA
Check
Part 6 Service Diagnosis
195
Note
8.7 Inverter
Analyzer
Check
Check No.15
Characteristics
Inverter analyzer: RSUK0917C
If an abnormal stop occurs due to compressor startup failure or overcurrent output when using an
inverter unit, it is difficult to judge whether the stop is caused by the compressor failure or some
other failure (main PCB, power module, etc.). The inverter analyzer makes it possible to judge the
cause of trouble easily and securely. Connect an inverter analyzer as a quasi-compressor instead
of compressor and check the output of the inverter.
Operation Method
Step 1
Be sure to turn the power off.
Step 2
Install an inverter analyzer instead of a compressor.
Note:
Make sure the charged voltage of the built-in smoothing electrolytic capacitor drops to 10 VDC or
below before carrying out the service work.
R6000682
Reference:
If the terminals of the compressor are not FASTON terminals (difficult to remove the wire on the
terminals), it is possible to connect wires available on site to the outdoor unit from output side of
PCB. Do not connect them to the compressor at the same time, otherwise it may result in incorrect
detection.
Step 3
Activate the power transistor test operation from the outdoor unit.
Power transistor test operation can be activated only once after turning on the power supply.
If reactivation of the power supply transistor operation is needed, turn the power supply off and then
on again.
(1) Remove the terminals from
the compressor.
(2) Connect the terminals to the
terminals of the inverter
analyzer.
Compressor
Inverter analyzer
Be careful not to let the terminals (U,V,W)
touch each other. Otherwise, high voltage
is applied.
Compressor
Содержание RX-W Series
Страница 1: ... Applied Models Inverter Pair Heat Pump Service Manual SiUS092230EA Inverter Pair RX W Series ...
Страница 15: ...SiUS092230EA Part 1 General Information 9 1 Applicable Models 10 2 Functions 11 Part 1 General Information ...
Страница 107: ...SiUS092230EA BRC082A41W BRC082A42W S Part 5 Remote Controller 101 4 BRC082A41W BRC082A42W S R23936 R23937 ...
Страница 151: ...SiUS092230EA Troubleshooting for FDMQ FFQ Series Part 6 Service Diagnosis 145 Reference Check No 02 Refer to P 191 ...
Страница 207: ...SiUS092230EA Check Part 6 Service Diagnosis 201 15 18 24 class R25105 1 2 3 4 Multimeter ...
Страница 209: ...SiUS092230EA Check Part 6 Service Diagnosis 203 15 18 24 class R20704 W V U DC_P1 DC_N1 ...
Страница 238: ...Piping Diagrams SiUS092230EA 232 Part 8 Appendix 1 2 Outdoor Unit RX09 12WMVJU9 RX15 18WMVJU9 3D135014 3D141501 ...
Страница 239: ...SiUS092230EA Piping Diagrams Part 8 Appendix 233 RX24WMVJU9 3D141502 ...
Страница 246: ...Operation Limit SiUS092230EA 240 Part 8 Appendix 3 Operation Limit RX09 12 15 18 24WMVJU9 3D092209F ...