background image

5

English

3.

SELECTION OF LOCATION

This unit does not have specifications for outdoor installation. The 
unit must be installed indoors (example: machine room, …).

Paying attention to the conditions mentioned below, select the place for 
installation with a prior approval of customer.

1.

The foundation is strong enough to support the weight of the unit and 
the floor is flat to prevent vibration and noise generation.

2.

Consider the space required for refrigerant piping work when install-
ing. Refer to [Necessary Space].

3.

There is no danger of fire due to leakage of inflammable gas.

4.

The piping length between the outside unit and the indoor unit may 
not exceed the allowable piping length. “

9. REFRIGERANT PIPING

”.

5.

Locations where the noise of the unit operating will not disturb 
nearby houses, etc.

6.

Locations with airflow and ventilation holes capable of dissipating 
heat from the machine and where the ambient temperature around 
the outside unit is between 35 and 95 °F and the humidity does not 
exceed 80%.

[Necessary Space]

When installing, secure the space mentioned below without fail.

(Refer to figure 2)

1.

In case of a single installation [inch.]

2.

In case of series installations [inch.]

3.

Top view

4.

Side view

5.

Outside unit

6.

Service Space (front side)

7.

Service Space (back side)

8.

Space for installing water piping

Secure a enough space for removing the front panel.

9.

Ventilation Space

above the area (

) of the outside unit.

10.

Secure spaces in the front, back and top sides as same as 
the case of single installation.

DANGER

Do not install unit in an area where flammable materials are 
present due to risk of explosion resulting in serious injury or death.

Refrigerant is heavier than air and replaces oxygen. A massive leak 
could lead to oxygen depletion, especially in basements, and an as-
phyxiation hazard could occur leading to serious injury or death. Re-
fer to the chapter “Caution for refrigerant leaks”.

NOTE

1.

An inverter air conditioner may cause electronic noise generated 
from AM broadcasting. Examine where to install the main air con-
ditioner and electric wires, keeping proper distances away from 
stereo equipment, personal computers, etc. 

(Refer to figure 3)

1.

Indoor unit

2.

Branch switch, overcurrent breaker

3.

Remote controller

4.

Cool/heat selector

5.

Personal computer or radio

If the electric wave of AM broadcasting is particularly weak, keep dis-
tances of 10 ft or more and use conduit tubes for power and trans-
mission lines.

2.

Water quality
Water containing high level of foreign materials may cause the 
corrosion of heat exchanger and piping or scale accumulation. 
Use water satisfying “7-4 Water quality”.

3.

Cooling tower
Use a closed type cooling tower without fail. (Open type tower 
cannot be used.)

4.

Strainer
Install the strainer (accessory) without fail at the inlet of water pip-
ing. (If sands, wastes, rust particles, etc. are mixed in the water cir-
culation system, damage to the plate type heat exchanger may be 
caused by the corrosion of metal materials and clogging of the 
heat exchanger.)

WARNING

Do not install in the following locations.

• Locations such as kitchens which contain a lot of mineral oil or steam 

in the atmosphere or where oil may splatter on the unit.
Resin parts may deteriorate, causing the unit to fall or leak.

• Locations where sulfurous acids and other corrosive gases may be 

present in the atmosphere.
Copper piping and soldered joints may corrode, causing refrigerant 
to leak.

• Locations where equipment that produces electromagnetic waves is 

found.
The electromagnetic waves may cause the control system to mal-
function, preventing normal operation.

4.

INSPECTING AND HANDLING THE UNIT

At delivery, the package should be checked and any damage should be 
reported immediately to the carrier claims agent.

When handling the unit, take into account the following:

1.

Fragile, handle the unit with care.

Keep the unit upright in order to avoid compressor damage.

2.

Choose the path along which the unit is to be brought in ahead of 
time.

3.

In order to prevent any damage to the unit during installation, use 
slings (cloth) or patch plates and lift the unit referring to figure 4.

4.

Lift the unit preferably with a crane and 2 belts of at least 27 ft long.

5.

When lifting the unit with a crane, always use protectors to prevent 
belt damage and pay attention to the position of the unit’s center of 
gravity.

6.

Be sure use the standard supplied accessories and dedicated parts 
as installation parts.

(Refer to figure 4)

1.

Patch plates or clothes

2.

Belt sling

NOTE

Use belt sling of 13/16” width or less which adequately bears the 
weight of the product. 

5.

UNPACKING AND PLACING THE UNIT

• Make sure the area around the machine drains properly by setting up 

drainage grooves around the foundation.

• Make sure the unit is installed level on a sufficiently strong base to 

prevent vibration and noise.

• Secure the unit to its base using foundation bolts. (Use four commer-

cially available M12-type foundation bolts, nuts, and washers.)

• The foundation bolts should be inserted 13/16”.
• Fix 4 foundation bolts.
• Support the unit with the foundation which is 

larger than the hatched area shown in figure 5.

(Refer to figure 5)

1.

Front side

2.

Position of foundation bolts

3.

Hole for a foundation bolt
(

φ

11/16 ida. holes at 4 corners)

4.

Avoid such a foundation where the unit is supported by 
4 corner points.

CAUTION

When installing the unit closely contacting the wall for any 
unavoidable reason, arrange so that no vibration from the unit may 
be transmitted to the wall surface by insulating the vibration using 
cushions, etc.

13/16”

Содержание RWEYQ144PTJU

Страница 1: ...for future reference This manual should be left with the equipment owner Lire soigneusement ces instructions avant I installation Concerver ce manuel port e de main pour r f rence ult rieure Ce manuel...

Страница 2: ...6 13 16 3 15 16 9 13 16 21 5 8 30 11 16 9 9 8 10 8 9 7 7 6 6 6 9 7 8 5 8 15 3 8 4 3 1 2 11 13 16 39 3 8 35 7 16 19 11 16 1 2 3 4 4 10 5 6 5 4 9 6 7 7 10 8 1 2 3 4 9 Heat recovery system Heat pump syst...

Страница 3: ...figure 13 figure 12 figure 11 A B C A B C F1 F1 F2 F2 Q1 Q2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 4 5 6 1 2 7 C H SELECTOR TO IN D UNIT TO OUT D UNIT TO MULTI UNIT 3 A B C F1 F1 F2 F2...

Страница 4: ...very system 1 2 3 4 5 6 7 8 9 10 11 5 4 12 14 15 16 17 13 figure 16 A B C A B C 1 DS1 1 2 3 4 OFF ON O U T I N TO IN D UNIT F1 F2 A1P A1P DS1 1 2 3 4 OFF ON O U T I N F1 F2 P1 P2 P1 P2 1 1 2 6 3 3 4 5...

Страница 5: ...4 5 6 Heat pump system Heat recovery system 4 5 3 2 1 figure 24 1 11 1 2 2 4 3 4 3 5 5 R410A R410A 9 7 7 8 13 9 6 6 16 10 10 10 10 17 12 12 14 15 15 18 18 Heat pump system Heat recovery system 1 2 3...

Страница 6: ...sult in equipment or property damage accidents only DANGER Refrigerant gas is heavier than air and replaces oxygen A massive leak can lead to oxygen depletion especially in base ments and an asphyxiat...

Страница 7: ...on tribute to the greenhouse effect if it is released Therefore take proper measures to check for the tightness of the refrig erant piping installation Read the chapter Refrigerant Pip ing and follow...

Страница 8: ...itches off automatically in order to protect the unit from freezing Hold ambient temperature at 35 95 F Heat release from the unit 0 64 kW hour Model 72 84 It is therefore recommended to always ventil...

Страница 9: ...emale Thread 1 2FPS 2 female Thread General RWEYQ216PTJU RWEYQ252PTJU Nominal cooling capacity 2 MBh 216 252 Nominal cooling capacity 3 MBh 243 283 5 Nominal input cooling heating 4 kW 12 60 12 00 16...

Страница 10: ...ower without fail Open type tower cannot be used 4 Strainer Install the strainer accessory without fail at the inlet of water pip ing If sands wastes rust particles etc are mixed in the water cir cula...

Страница 11: ...manner 7 1 When designing the equipment 1 Install the strainer accessory at the water inlet side adjacent to the outside unit in order to prevent any foreign materials such as dust sand etc from ente...

Страница 12: ...within the standard 2 Clean the strainer 3 Make sure that the flow rate is correct 4 Make sure that the operational conditions pressure flow rate outlet temperature etc are normal 2 Because the plate...

Страница 13: ...fect but also may cause the capacitor to overheat due to high frequency waves Therefore never install a phase advancing capacitor Keep power imbalance within 2 of the supply rating 1 Large imbalance w...

Страница 14: ...electromagnetic switch for the water pump to each outside unit Select without fail an auxiliary a contact able to switch min imum load of DC15V 1mA When connecting for each outside unit Connect to the...

Страница 15: ...erminals for connections to the power terminal block When none is available follow the instructions below Do not connect wiring of different thicknesses to the power termi nal block Slack in the power...

Страница 16: ...s always required When installing the piping follow the instructions in the installation manual that comes with the kit Restriction for the installation of the outside unit multi connection piping kit...

Страница 17: ...cal piping with the provided insulation to prevent it from coming into contact with the casing Precautions for installation of units NOTE The outside unit multi connection piping kit that is sold sepa...

Страница 18: ...c d e f r s t g h j k l m n o p i 23 3 lbs Total length ft of liquid piping size at 7 8 0 235 lbs ft Total length ft of liquid piping size at 3 8 Total length ft of liquid piping size at 1 4 Total len...

Страница 19: ...etc this must be prevented by caulking the connections etc WARNING Be sure to insulate connection piping as touching them can cause burns 9 8 Checking of device and installation conditions Be sure to...

Страница 20: ...refrigerant 9 10 Stop valve operation procedure CAUTION Do not open the stop valve until 1 6 of 9 8 Checking of device and installation conditions are completed If the stop valve is left open without...

Страница 21: ...onfiguration on the main unit Any settings made on a sub unit will be ignored After this close the electrical compo nents box lid Always perform configuration after turning ON the power To learn the s...

Страница 22: ...rding to local regulations or standards The following standards may be applicable if local regulations are not available The VRV System like other air conditioning systems uses R410A as refrigerant R4...

Страница 23: ...e open ings above and below the door which are each equivalent in size to 0 15 or more of the floor area 3 Calculating the refrigerant density using the results of the calcula tions in steps 1 and 2 a...

Страница 24: ...1645 Wallace Drive Suite 110 Carrollton TX 75006 info daikinac com www daikinac com 3P153897 12P EM09A022 0910 FS...

Отзывы: