background image

English

10

Field line connection:

L1, L2, L3, phase of the power supply wiring should be clamped to the 
safety catch using the included clamp material.
The green and yellow striped wrapped wires should be used for ground-
ing.
Make sure to connect the power wire to the power terminal block and fix 
it using attached clamp as shown in figure 15 and 19.

(Refer to figure 15)

1.

Power supply
(208-230V, Three-phase)

2.

Branch switch, overcurrent breaker

3.

Grounding wire

4.

Ground fault circuit interrupter

5.

Attach insulation sleeves.

6.

Power supply terminal block

7.

Grounding terminal

8.

Retain the ground wires along with the power wires using 
the accessory clamp (A).

9.

Grounding wire

10.

When wiring, do not allow the ground wires to contact the 
compressor lead wires. If the wires contact each other, 
adverse effects may occur to other units.

11.

When connecting two wires to one terminal, ensure that the 
crimp-style terminals face with each other back to back.
Moreover, make sure that the wire of the smaller gauge is 
located above.

12.

Terminal block

13.

Crimp-style terminal

14.

Wire gauge: Small

15.

Wire gauge: Large

(Refer to figure 19)

1.

Intake for power supply wiring, pump operation output (high 
voltage) and ground wiring.

2.

Stop valve for discharge gas (high temperature part)

3.

Insert the accessory clamp (B) in the hole of the fixing plate 
for stop valve.

4.

Power supply wiring, pump operation output (high voltage) 
and ground wiring.

5.

Retain the power supply wiring, pump operation output 
(high voltage) and ground wiring with the accessory clamp 
(B) to prevent them from touching with the stop valve for dis-
charge gas.

6.

Insert the accessory clamp (B) in the hole of the bottom of 
electrical box.

7.

Intake for transmission wiring. (low voltage)

8.

Make sure to provide for a downward loop in the transmis-
sion wiring right in front of the location where the wiring is to 
be fixed over the topplate of the switch box. This in order to 
prevent that condensate drips off the wiring into the switch 
box.

9.

Fix the transmission wiring to resin clamps with the acces-
sory clamps (A)

10.

Pass the transmission wiring (low voltage) through the wire 
clip.

11.

Retain the power supply wiring, pump operation output 
(high voltage) and ground wiring to the bottom of electrical 
box with the accessory clamp (B)

WARNING

• Use only specified wire and connect wires to terminals tightly.  Be 

careful that wires do not place external stress on terminals. Keep 
wires in neat order so as not to obstruct other equipment. Incom-
plete connections could result in overheating, and in worse cases, 
electric shock or fire.

CAUTION

Precautions when laying power wiring

Use round pressure terminals for connections to the power terminal 
block.

When none is available, follow the instructions below.

Do not connect wiring of different thicknesses to the power termi-
nal block. (Slack in the power wiring may cause abnormal heat.)

When connecting wiring which is the same thickness, do as 
shown in the figure below.

For wiring, use the designated power wire and connect firmly, 
then secure to prevent outside pressure being exerted on the ter-
minal board.

Use an appropriate screwdriver for tightening the terminal 
screws. A screwdriver with a small head will strip the head and 
make proper tightening impossible.

Over-tightening the terminal screws may break them.

See the table below for tightening torque for the terminal screws.

Precautions when connecting the ground

When pulling the ground wire out, wire it so that it comes through the 
cut out section of the cup washer. (An improper ground connection 
may prevent a good ground from being achieved.)

8-5 In case of a local setting

If necessary, do the local settings as mentioned in the table below. For 
setting, refer to the plate “Cares to be taken in servicing” attached to the 
cover of electrical components box.

Typical local settings

For other settings than mentioned in the table below, refer to the  
equipment design materials and service manual.

CAUTION

A separate adapter (sold separately as an accessory) for external 
control of an outside unit is necessary when doing a demand oper-
ation from an external instruction, setting of cooling and heating 
through a centralized remote controller for cooling and heating 
(sold separately as an accessory) and setting of centralized inter-
lock. For details, refer to the manual attached to the adapter.

Tightening torque

(ft · lbf)

M5 (Power terminal block)

2.21-3.02

M5 (Ground)
M3 (Transmission wiring terminal block)

0.59-0.72

(1) Setting of switching between 

cooling and heating

This setting is done when switching between cooling and 
heating is performed by a switching remote controller (sold 
separately as an accessory) installed on the outside unit.

(2) Setting to prohibit sequenced 

start

This setting is done when the outside units are not started in 
a sequenced order.

(3) Setting of centralized interlock 

Setting of external demand

These settings are done when the interlocks are connected 
in a lump-sum manner or when performing a demand opera-
tion by external instruction.

(4) Setting of abnormal display 

when interlock contact is OFF

This setting is done when making an abnormal display (HJ) 
on a remote controller when the interlock contact is OFF 
(when the heat source water pump is not operated).

Power wire

Round pressure
terminal

Connect same-
thickness wiring
to both sides.

It is forbidden to
connect two to
one side.

It is forbidden to
connect wiring of
different thicknesses.

Round pressure terminal

Cup washer

Cut out section 

Содержание RWEYQ144PTJU

Страница 1: ...for future reference This manual should be left with the equipment owner Lire soigneusement ces instructions avant I installation Concerver ce manuel port e de main pour r f rence ult rieure Ce manuel...

Страница 2: ...6 13 16 3 15 16 9 13 16 21 5 8 30 11 16 9 9 8 10 8 9 7 7 6 6 6 9 7 8 5 8 15 3 8 4 3 1 2 11 13 16 39 3 8 35 7 16 19 11 16 1 2 3 4 4 10 5 6 5 4 9 6 7 7 10 8 1 2 3 4 9 Heat recovery system Heat pump syst...

Страница 3: ...figure 13 figure 12 figure 11 A B C A B C F1 F1 F2 F2 Q1 Q2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 4 5 6 1 2 7 C H SELECTOR TO IN D UNIT TO OUT D UNIT TO MULTI UNIT 3 A B C F1 F1 F2 F2...

Страница 4: ...very system 1 2 3 4 5 6 7 8 9 10 11 5 4 12 14 15 16 17 13 figure 16 A B C A B C 1 DS1 1 2 3 4 OFF ON O U T I N TO IN D UNIT F1 F2 A1P A1P DS1 1 2 3 4 OFF ON O U T I N F1 F2 P1 P2 P1 P2 1 1 2 6 3 3 4 5...

Страница 5: ...4 5 6 Heat pump system Heat recovery system 4 5 3 2 1 figure 24 1 11 1 2 2 4 3 4 3 5 5 R410A R410A 9 7 7 8 13 9 6 6 16 10 10 10 10 17 12 12 14 15 15 18 18 Heat pump system Heat recovery system 1 2 3...

Страница 6: ...sult in equipment or property damage accidents only DANGER Refrigerant gas is heavier than air and replaces oxygen A massive leak can lead to oxygen depletion especially in base ments and an asphyxiat...

Страница 7: ...on tribute to the greenhouse effect if it is released Therefore take proper measures to check for the tightness of the refrig erant piping installation Read the chapter Refrigerant Pip ing and follow...

Страница 8: ...itches off automatically in order to protect the unit from freezing Hold ambient temperature at 35 95 F Heat release from the unit 0 64 kW hour Model 72 84 It is therefore recommended to always ventil...

Страница 9: ...emale Thread 1 2FPS 2 female Thread General RWEYQ216PTJU RWEYQ252PTJU Nominal cooling capacity 2 MBh 216 252 Nominal cooling capacity 3 MBh 243 283 5 Nominal input cooling heating 4 kW 12 60 12 00 16...

Страница 10: ...ower without fail Open type tower cannot be used 4 Strainer Install the strainer accessory without fail at the inlet of water pip ing If sands wastes rust particles etc are mixed in the water cir cula...

Страница 11: ...manner 7 1 When designing the equipment 1 Install the strainer accessory at the water inlet side adjacent to the outside unit in order to prevent any foreign materials such as dust sand etc from ente...

Страница 12: ...within the standard 2 Clean the strainer 3 Make sure that the flow rate is correct 4 Make sure that the operational conditions pressure flow rate outlet temperature etc are normal 2 Because the plate...

Страница 13: ...fect but also may cause the capacitor to overheat due to high frequency waves Therefore never install a phase advancing capacitor Keep power imbalance within 2 of the supply rating 1 Large imbalance w...

Страница 14: ...electromagnetic switch for the water pump to each outside unit Select without fail an auxiliary a contact able to switch min imum load of DC15V 1mA When connecting for each outside unit Connect to the...

Страница 15: ...erminals for connections to the power terminal block When none is available follow the instructions below Do not connect wiring of different thicknesses to the power termi nal block Slack in the power...

Страница 16: ...s always required When installing the piping follow the instructions in the installation manual that comes with the kit Restriction for the installation of the outside unit multi connection piping kit...

Страница 17: ...cal piping with the provided insulation to prevent it from coming into contact with the casing Precautions for installation of units NOTE The outside unit multi connection piping kit that is sold sepa...

Страница 18: ...c d e f r s t g h j k l m n o p i 23 3 lbs Total length ft of liquid piping size at 7 8 0 235 lbs ft Total length ft of liquid piping size at 3 8 Total length ft of liquid piping size at 1 4 Total len...

Страница 19: ...etc this must be prevented by caulking the connections etc WARNING Be sure to insulate connection piping as touching them can cause burns 9 8 Checking of device and installation conditions Be sure to...

Страница 20: ...refrigerant 9 10 Stop valve operation procedure CAUTION Do not open the stop valve until 1 6 of 9 8 Checking of device and installation conditions are completed If the stop valve is left open without...

Страница 21: ...onfiguration on the main unit Any settings made on a sub unit will be ignored After this close the electrical compo nents box lid Always perform configuration after turning ON the power To learn the s...

Страница 22: ...rding to local regulations or standards The following standards may be applicable if local regulations are not available The VRV System like other air conditioning systems uses R410A as refrigerant R4...

Страница 23: ...e open ings above and below the door which are each equivalent in size to 0 15 or more of the floor area 3 Calculating the refrigerant density using the results of the calcula tions in steps 1 and 2 a...

Страница 24: ...1645 Wallace Drive Suite 110 Carrollton TX 75006 info daikinac com www daikinac com 3P153897 12P EM09A022 0910 FS...

Отзывы: