background image

17

English

Cautions for check operation

• If the system is started within about 12 minutes after the outdoor/

indoor units are turned ON, the compressor will not run and H2P 
lights up. Before starting an operation, always verify that the LED dis-
play shows the contents of the table in “

11-3 Check operation

 (6)”.

• The system may require up to 10 minutes until it can start the com-

pressor after an operation start. This is a normal operation to equal-
ize the refrigerant distribution.

• The check operation does not provide any means of checking the 

indoor units individually. For that purpose, perform normal operation 
using the remote controller after the check operation.

• Check operation is not possible in other modes such as collection 

mode.

• If the setting of indoor remote controller is changed before the check 

operation, it may not be performed correctly and malfunction code 
“UF” may be displayed.

Remote controller displays malfunction code

11-4 Check of normal operation

After the check operation is completed, operate the unit normally. (Heat-
ing is not possible if the outdoor temperature is 75 °F or higher. Refer to 
the Operation manual.)
Check the below items.

Make sure the indoor and outside units are operating normally (If 
a knocking sound can be heard in the liquid compression of the 
compressor, stop the unit immediately and then energize the 
heater for a sufficient length of time before restarting the opera-
tion.)

Run each indoor unit one at a time and make sure the corre-
sponding outside unit is also running.

Check to see if cold (or hot) air is coming out of the indoor unit.

Press the fan direction and fan strength buttons on the indoor unit 
to check if they operate properly.

NOTE

Cautions for normal operation check

Once stopped, the compressor will not restart in about 5 minutes 
even if the 

Run/Stop

 button of an indoor unit in the same system 

is pressed.

When the system operation is stopped by the remote controller, 
the outside units may continue operating for further 5 minutes at 
maximum.

If the system has not undergone any check operation by the test 
operation button since it was first installed, an malfunction code 
“U3” is displayed. In this case, perform check operation referring 
to “

11-3 Check operation

”.

After the test operation, when handing the unit over to the cus-
tomer, make sure the electric box lid, the service lid, and the unit 
casing are all attached.

12. CAUTION FOR REFRIGERANT LEAKS

DANGER

Refrigerant gas is heavier than air and replaces oxygen. A massive 
leak could lead to oxygen depletion, especially in basements, and 
an asphyxiation hazard could occur leading to serious injury or 
death.

(Points to note in connection with refrigerant leaks)

Introduction

The installer and system specialist shall secure safety against 
leakage according to local regulations or standards. The following 
standards may be applicable if local regulations are not available.

The VRV System, like other air conditioning systems, uses R410A as 
refrigerant. R410A itself is an entirely safe non-toxic, non-combustible 
refrigerant. Nevertheless care must be taken to ensure that air condi-
tioning facilities are installed in a room which is sufficiently large. This 
assures that the maximum concentration level of refrigerant gas is not 
exceeded, in the unlikely event of major leak in the system and this in 
accordance to the local applicable regulations and standards.

Maximum concentration level

The maximum charge of refrigerant and the calculation of the maximum 
concentration of refrigerant is directly related to the humanly occupied 
space in to which it could leak.

The unit of measurement of the concentration is lb./ft

3

 ( the weight in lb. 

of the refrigerant gas in 1ft

3

 volume of the occupied space).

Compliance to the local applicable regulations and standards for the 
maximum allowable concentration level is required.

1.

direction of the refrigerant flow

2.

room where refrigerant leak has occurred (outflow of all the 
refrigerant from the system)

Malfunc-

tion code

Installation error

Remedial action

E3
E4
F3
F6

UF
U2

The stop valve of an out-
side unit is left closed.

Open the stop valve.
Check referring to the table in 

9-9 Additional refrigerant 

charge

”.

U1

The phases of the power 
to the outside units are 
reversed.

Exchange two of the three 
phases (L1, L2, L3) to make a 
positive phase connection.

U1
U2
U4

No power is supplied to 
an outside or indoor unit 
(including phase interrup-
tion).

Check if the power wiring for the 
outside units are connected cor-
rectly.
(If the power wire is not con-
nected to L2 phase, no malfunc-
tion display will appear and the 
compressor will not work.)
Check if the ground fault circuit 
interrupter in the outside unit is 
ON.

UF

Incorrect transmission 
between units

Check if the refrigerant piping 
line and the unit transmission 
wiring are consistent with each 
other.

E3
F6

UF
U2

Refrigerant overcharge

Recalculate the required 
amount of refrigerant from the 
piping length and correct the 
refrigerant charge level by 
recovering any excessive refrig-
erant with a refrigerant recovery 
machine.

E4
F3

Insufficient refrigerant

Check if the additional refrig-
erant charge has been fin-
ished correctly.

Recalculate the required 
amount of refrigerant from the 
piping length and add an ade-
quate amount of refrigerant.

U7
UF

If an outside multi termi-
nal is connected when 
there is one outside unit 
installed

Remove the line from the outside 
multi terminals (Q1 and Q2).

UF

E4

The operation mode on 
the remote controller was 
changed before the check 
operation.

Set the operation mode on all 
indoor unit remote controllers to 
“cooling.”

HJ

The heat source water is 
not circulating.

Make sure that the water pump 
is running.

U3

The check operation has 
not been performed.

Perform the check operation.

2

1

Содержание RWEYQ144PTJU

Страница 1: ...for future reference This manual should be left with the equipment owner Lire soigneusement ces instructions avant I installation Concerver ce manuel port e de main pour r f rence ult rieure Ce manuel...

Страница 2: ...6 13 16 3 15 16 9 13 16 21 5 8 30 11 16 9 9 8 10 8 9 7 7 6 6 6 9 7 8 5 8 15 3 8 4 3 1 2 11 13 16 39 3 8 35 7 16 19 11 16 1 2 3 4 4 10 5 6 5 4 9 6 7 7 10 8 1 2 3 4 9 Heat recovery system Heat pump syst...

Страница 3: ...figure 13 figure 12 figure 11 A B C A B C F1 F1 F2 F2 Q1 Q2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 4 5 6 1 2 7 C H SELECTOR TO IN D UNIT TO OUT D UNIT TO MULTI UNIT 3 A B C F1 F1 F2 F2...

Страница 4: ...very system 1 2 3 4 5 6 7 8 9 10 11 5 4 12 14 15 16 17 13 figure 16 A B C A B C 1 DS1 1 2 3 4 OFF ON O U T I N TO IN D UNIT F1 F2 A1P A1P DS1 1 2 3 4 OFF ON O U T I N F1 F2 P1 P2 P1 P2 1 1 2 6 3 3 4 5...

Страница 5: ...4 5 6 Heat pump system Heat recovery system 4 5 3 2 1 figure 24 1 11 1 2 2 4 3 4 3 5 5 R410A R410A 9 7 7 8 13 9 6 6 16 10 10 10 10 17 12 12 14 15 15 18 18 Heat pump system Heat recovery system 1 2 3...

Страница 6: ...sult in equipment or property damage accidents only DANGER Refrigerant gas is heavier than air and replaces oxygen A massive leak can lead to oxygen depletion especially in base ments and an asphyxiat...

Страница 7: ...on tribute to the greenhouse effect if it is released Therefore take proper measures to check for the tightness of the refrig erant piping installation Read the chapter Refrigerant Pip ing and follow...

Страница 8: ...itches off automatically in order to protect the unit from freezing Hold ambient temperature at 35 95 F Heat release from the unit 0 64 kW hour Model 72 84 It is therefore recommended to always ventil...

Страница 9: ...emale Thread 1 2FPS 2 female Thread General RWEYQ216PTJU RWEYQ252PTJU Nominal cooling capacity 2 MBh 216 252 Nominal cooling capacity 3 MBh 243 283 5 Nominal input cooling heating 4 kW 12 60 12 00 16...

Страница 10: ...ower without fail Open type tower cannot be used 4 Strainer Install the strainer accessory without fail at the inlet of water pip ing If sands wastes rust particles etc are mixed in the water cir cula...

Страница 11: ...manner 7 1 When designing the equipment 1 Install the strainer accessory at the water inlet side adjacent to the outside unit in order to prevent any foreign materials such as dust sand etc from ente...

Страница 12: ...within the standard 2 Clean the strainer 3 Make sure that the flow rate is correct 4 Make sure that the operational conditions pressure flow rate outlet temperature etc are normal 2 Because the plate...

Страница 13: ...fect but also may cause the capacitor to overheat due to high frequency waves Therefore never install a phase advancing capacitor Keep power imbalance within 2 of the supply rating 1 Large imbalance w...

Страница 14: ...electromagnetic switch for the water pump to each outside unit Select without fail an auxiliary a contact able to switch min imum load of DC15V 1mA When connecting for each outside unit Connect to the...

Страница 15: ...erminals for connections to the power terminal block When none is available follow the instructions below Do not connect wiring of different thicknesses to the power termi nal block Slack in the power...

Страница 16: ...s always required When installing the piping follow the instructions in the installation manual that comes with the kit Restriction for the installation of the outside unit multi connection piping kit...

Страница 17: ...cal piping with the provided insulation to prevent it from coming into contact with the casing Precautions for installation of units NOTE The outside unit multi connection piping kit that is sold sepa...

Страница 18: ...c d e f r s t g h j k l m n o p i 23 3 lbs Total length ft of liquid piping size at 7 8 0 235 lbs ft Total length ft of liquid piping size at 3 8 Total length ft of liquid piping size at 1 4 Total len...

Страница 19: ...etc this must be prevented by caulking the connections etc WARNING Be sure to insulate connection piping as touching them can cause burns 9 8 Checking of device and installation conditions Be sure to...

Страница 20: ...refrigerant 9 10 Stop valve operation procedure CAUTION Do not open the stop valve until 1 6 of 9 8 Checking of device and installation conditions are completed If the stop valve is left open without...

Страница 21: ...onfiguration on the main unit Any settings made on a sub unit will be ignored After this close the electrical compo nents box lid Always perform configuration after turning ON the power To learn the s...

Страница 22: ...rding to local regulations or standards The following standards may be applicable if local regulations are not available The VRV System like other air conditioning systems uses R410A as refrigerant R4...

Страница 23: ...e open ings above and below the door which are each equivalent in size to 0 15 or more of the floor area 3 Calculating the refrigerant density using the results of the calcula tions in steps 1 and 2 a...

Страница 24: ...1645 Wallace Drive Suite 110 Carrollton TX 75006 info daikinac com www daikinac com 3P153897 12P EM09A022 0910 FS...

Отзывы: